Yokogawa Optical ESB Bus Repeater Module SNT401-5F/CU1T[Product print page]

Product Name: Yokogawa Optical ESB Bus Repeater Module SNT401-5F/CU1T
Product Type: SNT401-5F/CU1T
Exhibitors: Yokogawa
Product Documentation: No Related Documents

Brief

Yokogawa Optical ESB Bus Repeater Module SNT401-5F/CU1T


 Detailed description

Yokogawa Optical ESB Bus Repeater Module SNT401-5F/CU1T

The Optical ESB Bus Repeater Module converts ESB Bus, which connects safety control unit (SSC60S/SSC60D, SSC50S/SSC50D, SSC10S/SSC10D) and safety node unit (SNB10D), to optical signal.

 

ESB Bus transmission distance can be extended by connecting Optical ESB Bus Repeater Master Module (SNT401) and Optical ESB Bus Repeater Slave Module (SNT501) with an optical fiber cable.

In case Vnet/IP is adapted as a control network, it is possible to use both Optical ESB Bus Repeater Master Module

(SNT411) and Optical ESB Bus Repeater Slave Module (SNT511)

 

SNT401 Optical ESB Bus Repeater Master Module

Yokogawa Optical ESB Bus Repeater Module SNT401-5F/CU1T

This module is connected from ESB Bus Coupler Module (SEC401, SEC402) on the safety control unit or ESB Bus

Interface Module (SSB401) on the safety node unit (SNB10D) through ESB Bus cable.

There are two types of ESB Bus Repeater Modules: with or without a terminator.

 

SNT501 Optical ESB Bus Repeater Slave Module

This module is connected from Optical ESB Bus Repeater Master Module through fiber-optic cable. Furthermore, it is connected through ESB Bus cable to ESB Bus Interface Module (SSB401) on the safety node unit (SNB10D).


STANDARD SPECIFICATIONS

Yokogawa Optical ESB Bus Repeater Module SNT401-5F/CU1T

Function:    ESB Bus optical transport function

Connection method:  Star type connection

Chain type connection

Available for both star and chain type connection. 

Number of connecting stage:     Maximum two

Transmission distance:    Maximum 5 km (total two stages)

In case of Vnet/IP system with the R1.03 or later, the total distance of two stages is maximum 10 km.

Current consumption:   0.5 A 

Weight:   0.3 kg

 

MODEL AND SUFFIX CODES

 Yokogawa Optical ESB Bus Repeater Module SNT401-5F/CU1T

 

 

Description

Model

SNT401

Optical ESB Bus Repeater Master Module

 

Suffix

Codes

-5

With no explosion protection

-E

With explosion protection

3

ISA Standard G3 and temperature (–20 to 70 °C)

 

Option

Codes

/CU1N

Connector unit for ESB Bus [Part Number: S9345FA]

/CU1T

Connector unit with terminator for ESB Bus [Part Number: S9346FA]