Product Information

Yokogawa Analog Output Module NFAI543-S50/CCC01[Product print page]

Product Name: Yokogawa Analog Output Module NFAI543-S50/CCC01
Product Type: NFAI543-S50/CCC01
Exhibitors: Yokogawa
Product Documentation: No Related Documents

Brief

Yokogawa Analog Output Module NFAI543-S50/CCC01. Please feel free to contact us: tekrachel @ 163.com


 Detailed description

Manufacturer: Yokogawa Electric Corporation

STARDOM

FCN, FCN-500, FCN-100, FCN-RTU, FCJ

Yokogawa Analog Output Module NFAI543-S50/CCC01  

Standard Specifications

Current Output Modules (Isolated)

Output of 4 to 20 mA electric currents of 16 channels.

Yokogawa Analog Output Module NFAI543-S50/CCC01

Items

Specifications

Model

NFAI543 (*3)

Number of output channels

16-channel output, isolated

Output signal

4 to 20 mA

Withstanding voltage

Between output and system: 1500 V AC for 1 minute (*5)

Allowable load resistance

0 to 750 Ω

Circuit-open detection

0.65 mA or less

Accuracy

±0.3% of full scale

Data refresh cycle

10 ms

Output step response time

100 ms

Output fallback (*2)

Set for each channel (*1)

Temperature drift

Max. ±0.01%/°C

Maximum current

230 mA (5 V DC)

consumption

540 mA (24 V DC)

Weight

0.4 kg

External connection

Pressure clamp terminal, MIL connector cable (*5)

HART Communication(*4)

Available

*1:  HOLD: To hold output in which fallback is detected.
       SETV: To output a specified value when fallback is detected.
*2:  Select fallback [Yes/No] for each module.
       If [Yes] is selected for fallback, set [HOLD/SETV] for each channel.
       Fallback detection time: 4 seconds. Yokogawa Analog Output Module NFAI543-S50/CCC01
*3:  When this I/O module is used, 24 V DC needs to be supplied to an analog field power supply terminal of the power supply module.
*4:  For HART function specifications, refer to GS 34P02Q53-01E HART Communication Functions.
*5:  The withstanding voltage for using MIL connector cable depends on the electrical specifications of its cable. If you are using KMS40 cable, withstanding voltage of between input and system is 500 V AC for 1 minute. Yokogawa Analog Output Module NFAI543-S50/CCC01

Models and Suffix Codes 

Yokogawa Analog Output Module NFAI543-S50/CCC01

 

 

Description

Model

NFAI543

Analog Output Module (4 to 20mA,16-channel, Isolated)

 

 

 

Suffix Codes

-S

Standard Type

-H

With HART Communication

5

With no explosion protection

E

With explosion protection

0

Basic type

1

With ISA Standard G3 option

 

OptionCodes

/A4S00

With Pressure Clamp Terminal Block for Analog [Model: NFTA4S-00]

/A4S10

With Pressure Clamp Terminal Block for Analog (surge absorber) [Model: NFTA4S-10]

/CCC01

With Connector Cover for MIL Cable [Model: NFCCC01]