Product Information

Yokogawa ESB Bus Node Unit ANB10D-446[Product print page]

Product Name: Yokogawa ESB Bus Node Unit ANB10D-446
Product Type: ANB10D-446
Exhibitors: Yokogawa
Product Documentation: No Related Documents

Brief

Yokogawa ESB Bus Node Unit ANB10D-446. Yokogawa Centum VP, Yokogawa DCS. Please contact us: tekrachel @ 163.com


 Detailed description

Manufacturer: Yokogawa Electric Corporation

Control System: CENTUM VP

Yokogawa ESB Bus Node Unit ANB10D-446

The ESB Bus Node Unit has an interface function that communicates the analog I/O signals and contact I/O signals of a field with a Field Control Unit (FCU) via an ESB bus, as well as a function that supplies power to the I/O Modules.

This node units are connected to FCU via ESB bus.

ESB Bus Node Connection

Yokogawa ESB Bus Node Unit ANB10D-446

When connecting an ESB Bus Node Unit to FCU, install ESB Bus Couple Module (EC401 or EC402) to FCU (*1).

EC401 or EC402 must be installed in slot 7 and slot 8. To make single configuration, EC401 or EC402 must be installed in slot 7, and slot 8 must be empty.

Power Supply

Yokogawa ESB Bus Node Unit ANB10D-446

Specify with Suffix Codes

Voltage: 100-120 V AC, Frequency: 50/60 Hz

Voltage: 220-240 V AC, Frequency: 50/60 Hz

Voltage: 24 V DC

Electric Power Consumption

100-120 V AC: 200 VA, 120 W

220-240 V AC: 230 VA, 120 W

24 V DC: 5.5 A

Weight

10 kg (including 8 I/O Modules)