Product Information

Yokogawa ProSafe-RS Analog Input Module SDV144-S5C/B4S00[Product print page]

Product Name: Yokogawa ProSafe-RS Analog Input Module SDV144-S5C/B4S00
Product Type: SDV144-S5C/B4S00
Exhibitors: Yokogawa
Product Documentation: No Related Documents

Brief

Yokogawa ProSafe-RS Analog Input Module SDV144-S5C/B4S00. Please contact us: tekrachel @ 163.com


 Detailed description

Yokogawa ProSafe-RS Analog Input Module SDV144-S5C/B4S00

STANDARD SPECIFICATIONS

Yokogawa ProSafe-RS Analog Input Module SDV144-S5C/B4S00

 Input Module

 Yokogawa ProSafe-RS Analog Input Module SDV144-S5C/B4S00 accept contact signals from the field. SDV144-S5C/B4S00 can be made dual-redundant.

Item

Specifications

Model

SDV144

Number of inputs

16-channel, module isolation

 

Input signal

No-voltage contact ON: 1 k maximum OFF: 100 k minimum

 

Input current

6 mA ± 20 %

(External power supply, 24 V DC at 0 input)

Contact rating

24 V DC +20 % / -10 % (*1), 10 mA or greater

 

External power supply

24 V DC +20 % / -10 % (*1) Current capacity: 200 mA

Instantaneous maximum permissible input voltage

 

30.0 V DC

Input response time

40 ms maximum

Withstand voltage

2 kV AC between input signal and system, 16-input line collectively connected (*2)

 

Current consumption

290 mA maximum (5 V DC)

140 mA maximum (24 V DC)

 

Weight

0.36 kg (For pressure clamp terminal block or MIL cable)

0.41 kg (With signal cable interface adapter)

 

External connection

Pressure clamp terminal

MIL cable

Dedicated signal cable (AKB331)

*1:      The contact rating and the external power supply of SDV144-S5C/B4S00 style code S1, S2 and S3 are 24 V DC ± 5 %.

*2:      When connecting SDV144-S5C/B4S00 and SED4D terminal board using the dedicated signal cable, the withstand voltage is 500 V AC (between input signal lines and system). If MIL connector cables are used, the withstand voltage depends on their cable’s electrical specifications.

MODEL AND SUFFIX CODES

Yokogawa ProSafe-RS Analog Input Module SDV144-S5C/B4S00

Digital Input Module

 

 

Description

Model

SDV144

Digital Input Module (16-channel, module isolation)

 

 

 

 

Suffix Codes

-S

Standard type

5

For pressure clamp terminal block or MIL cable with no explosion protection

6

With signal cable interface adapter and no explosion protection (*1)

E

For pressure clamp terminal block or MIL cable with explosion protection

F

With signal cable interface adapter and explosion protection (*1)

3

With ISA Standard G3 and temperature (-20 to 70 °C)

 

 

 

 

 

Option Codes

/B4S00

With pressure clamp terminal block for digital input (without surge absorber) [Model: STB4S-00]

/B4S10

With pressure clamp terminal block for digital input (with surge absorber) [Model: STB4S-10]

 

/B4D00

Dual-redundant pressure clamp terminal block for digital input (without surge absorber) (*2) [Model: STB4D-00]

 

/B4D10

Dual-redundant pressure clamp terminal block for digital input (with surge absorber) (*2) [Model: STB4D-10]

/PRP

With prevention pin of false insertion (*3)

/CCC01

With connector cover for MIL cable (for flat ribbon cable) [Model: SCCC01]

/CCC02

With connector cover for MIL cable (for discrete wire) [Model: SCCC02]

*1:      When SDV144-S5C/B4S00-S63 or -SF3 is selected, you cannot choose the option code for a pressure clamp terminal block and MIL

cable connector.

*2:      When this module is used in dual-redundant configuration, order an additional module with the same specification but without option codes. Yokogawa ProSafe-RS Analog Input Module SDV144-S5C/B4S00

*3:      When SDV144-S5C/B4S00-S63 or -SF3 is selected, you can choose the option code for prevention pin of false insertion.