Product Information

Yokogawa Terminal Block NFTD5S[Product print page]

Product Name: Yokogawa Terminal Block NFTD5S
Product Type: NFTD5S
Exhibitors: Yokogawa
Product Documentation: No Related Documents

Brief

Yokogawa Terminal Block NFTD5S, Yokogawa Terminal Block NFTD5S, 32-channel, 24 V DC, Isolated. Please contact us: tekrachel @ 163.com


 Detailed description

Manufacturer: Yokogawa Electric Corporation

STARDOMFCN, FCN-500, FCN-100, FCN-RTU, FCJ

Yokogawa Terminal Block NFTD5S 

Standard Specifications

Digital Output Modules
The Digital Output Modules output 32-channel or 64-channel transistor contact signals.

Yokogawa Terminal Block NFTD5S

Item

Specifications

Model

NFDV551

NFDV557

NFDV561

Number of output channels

32

32

64

Rated applied voltage

24 V DC

24 V DC

24 V DC

Load voltage (*1)

24 V DC, 50 mA

24 V DC, 50 mA

24 V DC, 100 mA

Field power supply voltage range

 

20.4 to 26.4 V

 

20.4 to 26.4 V

 

20.4 to 26.4 V

Output ON voltage maximum value

 

2 V DC

 

2 V DC

 

2 V DC

Leak current maximum value when output OFF

 

0.1 mA

 

0.1 mA

 

0.1 mA

Output format

Current sink

Current sink

Current sink

Maximum load current (*2)

100 mA/channel, 26.4 V

100 mA/channel, 26.4 V

100 mA/channel, 26.4 V

 

Withstanding voltage

Between output signal and system: 2 kV AC (*5)

Between commons: 500 V AC, common minus (–) side every 16-channel

Functions

Status output

 

ON/OFF status output function

 

ON/OFF status output function

 

ON/OFF status output function

 

Output fallback (*3) (*4)

HOLD: Holds the current states when the fallback action is triggered.

OFF: Resets all the output channels to off when the fallback action is triggered. NO: Performs no fallback action.

Output response time

3 ms or less (for status output)

 

Maximum current consumption

700 mA (5 V DC)

60 mA (24 V DC, field power

supply)

550 mA (5 V DC)

60 mA (24 V DC, field power

supply)

780 mA (5 V DC)

120 mA (24 V DC, field power

supply)

Weight

0.2 kg

0.3 kg

0.3 kg

 

External connection

Pressure clamp terminal, MIL

connector cable (*5)

 

Pressure clamp terminal

 

MIL connector cable (*5)

*1: An external field power supply (24 V DC) is required for each module. 
*2: Connect a spark killer diode when driving DC relay. Yokogawa Terminal Block NFTD5S
*3: The fallback detection time is 4 seconds. 
*4: HOLD, OFF, or NO should be chosen for all channels commonly. Yokogawa Terminal Block NFTD5S
*5: The withstanding voltage for using MIL connector cable depends on the electrical specifications of its cable.

Models and Suffix Codes 

Digital Output Module

Yokogawa Terminal Block NFTD5S

 

 

Description

Model

NFDV551

Digital Output Module (32-channel, 24 V DC, Isolated)

 

 

Suffix Codes

-P

Standard type

6

With status display and no explosion protection

F

With status display and explosion protection

0

Basic type

1

With ISA Standard G3 option

 

Option Codes

/D5S00

With Pressure Clamp Terminal Block for Digital Output [Model : NFTD5S-00]

/D5S10

With Pressure Clamp Terminal Block for Digital Output (surge absorber) [Model : NFTD5S-10]

/CCC01

With Connector Cover for MIL Cable [Model : NFCCC01]