Manufacturer: Yokogawa Electric Corporation
STARDOM: FCN, FCN-500, FCN-100, FCN-RTU, FCJ
Yokogawa SB Bus T-joint NFSBT01 NFSBT02
Features
Yokogawa SB Bus T-joint NFSBT01 NFSBT02
• High-performance, high-reliability modular controller
• Memory with ECC
• Low heat dissipation eliminates the need for a fan
• A wealth of RAS features -CPU self-diagnostics, temperature monitoring, I/O diagnostics, and more
• The CPU, power supply module, local bus (SB bus), and control network can all be duplexed, and all modules are hot-swappable.
• Can function as link active schedulers (LASs) for low-speed voltage mode (H1) FOUNDATION Fieldbus segments, and link up FOUNDATION Fieldbus-enabled field devices.
Configuration
Yokogawa SB Bus T-joint NFSBT01 NFSBT02
An FCN-100 consists of the following:
• Base module
• Power supply module
• CPU module
• SB bus repeat module (extending the SB bus, the local bus for FCNs, to connect an extension unit)
• I/O modules
There are two types of base module.
- NFBU200 base module (long): Up to 2 extension units connectable for I/O expansion
- NFBU050 base module (short): Compact and dedicated to one-unit-configuration
Maximum I/O Module Configurations
Base Module
|
Unit Configuration
|
Standard
|
Duplexed (*1)
|
NFBU200 base module (long)
|
Control unit only
|
Max. 8 modules
|
Max. 6 modules
|
With 1 extension unit
|
Max. 16 modules
|
Max. 12 modules
|
With 2 extension unit
|
Max. 25 modules
|
Max. 20 modules
|
NFBU050 base module (short)
|
Control unit (*2)
|
Max. 3 modules
|
Not applicable (*3)
|
*1: When CPU and SB bus repeat modules are duplexed
*2: SB bus repeat modules cannot be mounted on NFBU050.
*3: Neither power supply nor CPU modules can be duplexed on NFBU050.
Installation Requirements
Yokogawa SB Bus T-joint NFSBT01 NFSBT02
Item
|
Specification
|
Ambient temperature
|
Operation
|
0° to 55°C
|
Transportation/storage
|
– 40° to 85°C (*1)
|
Ambient humidity
|
Operation
|
5 to 95 %RH (no condensation)
|
Transportation/storage
|
5 to 95 %RH (no condensation)
|
Rate of change in
temperature
|
Operation
|
Within ±10°C/h
|
Transportation/storage
|
Within ±20°C/h
|
Dust
|
0.3 mg/m3 or less
|
Protection class
|
IP20
|
Resistance to corrosive gases
|
ANSI/ISA S71.04 Class G2 (Standard) (ANSI/ISA S71.04 Class G3, option)
|
Resistance to vibration
|
0.15 mm P-P (5 to 58 Hz), 1 G (58 to 150 Hz)
|
Resistance to shock
|
15 G, 11 ms (during power-off, for sine half-waves in XYZ-directions)
|
Altitude
|
2000 m or less
|
Noise
|
Electric field
|
3 V/m or less (26 MHz to 1 GHz)
|
Magnetic field
|
30 A/m (AC) or less, 400 A/m (DC) or less
|
Electrostatic discharge
|
4 kV or less contact discharge, 8 kV or less aerial discharge
|
Grounding
|
Apply the grounding system which is defined by the rules and standards of the
country or the region.
|
Cooling
|
Natural air cooling
|
*1: System clock may be reset if the temperature falls below -10°C.
SB Bus Repeat Module
Used to connect a control unit to I/O extension units. To duplex the SB bus, install two SB bus repeat modules in each unit.
Each SB bus repeat module is connected to another via a dedicated T-joint and cable.
Model and Suffix Codes
Yokogawa SB Bus T-joint NFSBT01 NFSBT02
|
|
Description
|
Model
|
NFSB100
|
SB bus repeat module for FCN
|
Suffix
Codes
|
-S
|
Standard model
|
5
|
With no explosion protection
|
E
|
With explosion protection
|
0
|
Basic type
|
1
|
With ISA Standard G3 option
|
Option
Codes
|
/SBT01
|
With an SB bus T-joint
|
/SBT02
|
With an SB bus T-joint with built-in terminator
|
Note: When connecting a control unit and extension units, install at both ends a T-joint with built-in terminator on each SB bus repeat module.
|
|
Description
|
Models
|
NFSBT01
|
SB bus T-joint
|
|
NFSBT02
|
SB bus T-joint with built-in terminator
|
|
|
Description
|
Model
|
NFCB301
|
SB bus cable
|
Suffix
Codes
|
-C030
|
Cable length 30 cm
|
-C100
|
Cable length 1 m
|
-C200
|
Cable length 2 m
|
-C400
|
Cable length 4 m
|
-C800
|
Cable length 8 m
|