Product Information

Yokogawa Duplexed Field Control Unit AFG30D-H4123 for V net and FIO [Product print page]

Product Name: Yokogawa Duplexed Field Control Unit AFG30D-H4123 for V net and FIO
Product Type: AFG30D-H4123
Exhibitors: Yokogawa
Product Documentation: No Related Documents

Brief

Yokogawa Duplexed Field Control Unit AFG30D-H4123 for V net and FIO, Yokogawa Duplexed Field Control Unit AFG30D-H4123 for V net and FIO


 Detailed description

Manufacturer: Yokogawa Electric Corporation

Yokogawa Duplexed Field Control Unit AFG30D-H4123 for V net and FIO


HARDWARE SPECIFICATIONS

For the installation specifications and the environmental conditions common to the systems, refer to 'System Overview (GS 33K01A20-50E).'

 

Processor

  VR5432 (133 MHz)

 

Main Memory Capacity

  AFS30S, AFS30D: 16 Mbyte

  AFG30S, AFG30D: 32 Mbyte

 

Memory Protection During Power Failure

  Battery

  4 Back-up for Main Memory: Max. 72 hours

  Battery Recharge Time: Min. 48 hours

 

FCU Status Contact Output

  2 terminals (NC, C)

  Contact Points open during FCU failure

  Contact Rating: 30 V DC, max. 0.3 A

 

Communication Interface

  V net Interface: Dual-redundant

  ESB bus interface: Dual-redundant or Single

 

No. of Node Units Connectable

  Local Node units: Max.10/FCU

  Remote Node units:

           Max. 9/FCU

           Max. 8/ER Bus

  When both Local and Remote Node units used:

           Max.10/FCU

  However, when using Remote Node Expanded FCS database type at FCU model AFG30S or AFG30D,

  No. of Node comes to be shown below.

     Local Node units: Max.10/FCU

     Remote Node units:

           Max.14/FCU

           Max. 8/ER Bus

    When both Local and Remote Node units used:

           Max.15/FCU

Yokogawa Duplexed Field Control Unit AFG30D-H4123 for V net and FIO  

Power Supply

  (specify with Suf?x Codes)

  Voltage: 100-120 V AC, Frequency: 50/60 Hz

  Voltage:   220-240 V AC, Frequency: 50/60 Hz

  Voltage:   24 V DC

 

Power Consumption

   100-120 V AC: 250 VA (AFS30S, AFG30S)

                           400 VA (AFS30D, AFG30D)

    220-240 V AC: 250 VA (AFS30S, AFG30S)

                            410 VA (AFS30D, AFG30D)

    24 V DC: 4.5 A (AFS30S, AFG30S)

                    8 A (AFS30D, AFG30D)

Weight

   Approx. 20 kg (AFS30S, AFG30S)

  Approx. 25 kg (AFS30D, AFG30D)

Yokogawa Duplexed Field Control Unit AFG30D-H4123 for V net and FIO  

Mounting

   19-inch Rack Mounting:

                Rack mount (M5x8 screws)

                Insulation bush (accessory)

 

Connection

   Power Supply: M4 screw terminal connection

   Grounding: M4 screw terminal connection

   Contact Output: M4 screw terminal connection


Regulatory Compliance

   For the detailed information of following standards, see Integrated Production Control System CENTUM VP System

   Overview (GS 33K01A20-50E).

      Safety Standards

           [CSA]                      (for 100-120 V AC power supply)

           [CE Marking]          (for 220-240 V AC power supply)

      EMC Conformity Standards

           [CE Marking]           (for 220-240 V AC and 24 V DC power supply)

           [C-Tick Marking]      (for 220-240 V AC and 24 V DC power supply)

           [KC Marking]           (for 220-240 V AC and 24 V DC power supply)

Yokogawa Duplexed Field Control Unit AFG30D-H4123 for V net and FIO 

MODEL AND SUFFIX CODES

 Duplexed Field Control Unit (19-inch Rack Mountable Type)

 

 

Description

Model

AFG30D

Duplexed Field Control Unit (for V net and FIO, for 19” Rack Mountable)

Suffix Codes

-H

Standard Type (Main memory 32 Mbyte)

     4

Dual-Redundant V net, Dual-Redundant ESB bus

     E

Dual-Redundant Vnet, Dual-Redundant ESB bus with SOE interface (*1)

        1

Always 1

            1

100–120 V AC Power Supply

            2

220–240 V AC Power Supply

            4

24 V DC

                 3

LFS1330 Basic software license for Control Function for Enhanced Field Control Station(for V net and FIO, for CP345)

*1: Please order one terminator (Model YCB128) required on the IRIG-B branch unit at the FCS that comes at the end of the RS-422 time synchronization link.