GENERAL

Yokogawa Single Loop Controller YS1500-100

The YS1500-101 Indicating Controller incorporates fundamental control functions required for PID control. Necessary func- tions can be selected in accordance with the user’s purpose. The available functions include those functions necessary for input signal processing, such as square root extraction and linear segment conversion, and feed-forward calculation. Single-loop, cascade and selector mode is also available. Standard models are smaller and lighter than earlier series, requiring less space for installation, and are compliant with international safety standards including the CE Mark and FM*, CSA* nonincendive (optional) approvals. For easy replacement of earlier controllers, models requiring the same panel cutout dimensions and depth as those of earlier mod- els are also offered. *: To be approved.

Yokogawa Indicating Controller YS1500-101

FEATURES

• Excellent legibility thanks to a full-dot, TFT LCD: High vis- ibility of the display screen is ensured even in direct sunlight in the early morning and late afternoon. The user can 
freely access a desired operation display from meter, trend display, bar graph, alarm, and event displays. All parameters can be set via the front panel display.
• Function selection mode (needs no programming): The multi-function controller mode allows control to be selected from frequently used functions (single-loop, cascade, or selector control) without programming. Function assign- ments to digital and analog inputs/outputs (DIs, DOs, AIs, and AOs) can be determined by parameter settings.
• Fail-safe: Thanks to dual CPU (one for control and one for dis- play), display and manual operations are enabled even during a failure of either CPU. The hard manual circuit incorporated independently from the digital circuits enables the controller output to be adjusted manually during a failure of a digital circuit including both CPUs. (The hard manual circuit is not incorporated when the suffix code -2xx option is specified.)
• Nonvolatile memory for memory backup: No battery or ca-
pacitor is used for memory backup, facilitating maintenance.
•  AC/DC dual power supply with wide operating voltage range 
to ensure stability against supply voltage fluctuations: Can be driven by either an AC (100 V) or DC (24 V) power sup- ply. Furthermore, the DC power supply enables receiving power without polarity. (Must be specified upon ordering if using a 220 V AC power supply.)
• 250 mm depth (for basic types only)
• Dust- and splash-proof IP54 faceplate (for basic type only)

  CE Mark (for basic type and YS100 compliant type only)

•  FM Nonincendive explosion protection (optional for basic type only) (To be approved)

 CSA Nonincendive explosion protection (optional for basic type, compatible type for YS100 (with YS100 case)) (To be approved)

 Communication (optional)

- Ethernet (Modbus/TCP; for basic type only)

 RS485 (PC Link, Modbus and YS protocol; unavailable for YS80

internal unit-compatible type)

- DCS-LCS communication

 Compatibility with YS100 Series: Setting and control opera- tions can be done with the same feel. For basic-type cases, terminal-to-terminal pitches differ but the signal-to-terminal arrangement is almost the same.

Yokogawa Indicating Controller YS1500-101

  Model and Suffix Codes

Model

Suffix Code

Optional Code

Remarks

YS1500-100

 

Indicating controller

 

Use

-1

With hard manual unit

-2

Without hard manual unit

 

 

Type

0

Basic type

2

Compatible type for YS100 (with YS100 case)

3

Compatible type for YS80 internal unit/compatible type for EBS,I, EK, and HOMAC (*1)

4

Compatible type for YS80 (compatible size for YS80 with YS100terminal)

5

Compatible type for 100 line (with YS100 terminal) (*2)

 

Power supply

0

100 V AC, 24 V DC common power

1

220 V AC power

 

 

 

 

Direct input (*3)

/A01

mV input

/A02

Thermocouple input

/A03

RTD input

/A04

Potentiometer input

/A05

Isolator

/A06

Two-wire transmitter input (isolated)

/A07

Two-wire transmitter input (non-isolated)

/A08

Frequency input

/DF

Direct input with Fahrenheit temperature range function (*8)

 

Communication

/A31

RS-485 communication (PC-link, Modbus, YS protocol) (*4)

/A32

DCS-LCS communication (*5)

/A34

Ethernet communication (Modbus/TCP) (*6)

 

Certification

/FM

FM nonincendive approved (FM Class I, DIV 2) (*7) (To beapproved)