Product Information

Endress+Hauser (E+H) Ultrasonic Level Sensor FMU42[Product print page]

Product Name: Endress+Hauser (E+H) Ultrasonic Level Sensor FMU42
Product Type: FMU42
Exhibitors: Endress+Hauser E+H
Product Documentation: No Related Documents

Brief

Endress+Hauser (E+H) Ultrasonic Level Sensor FMU42, Endress+Hauser (E+H) Ultrasonic Level Sensor FMU42, for non-contact level measurement in fluids, pastes, coarse bulk material and flow measurement in open channels or at weirs.


 Detailed description

Ultrasonic measurement
Time-of-Flight
Prosonic FMU42

Endress+Hauser (E+H) Ultrasonic Level Sensor FMU42

Cost effective device for sophisticated level measurement in liquids and bulk solids for up to 10m
The Prosonic FMU42 sensor is suited for non-contact level measurement in fluids, pastes, coarse bulk material and flow measurement in open channels or at weirs. The two-wire or four-wire compact transmitter can be used in applications with storage tanks, agitators, on stockpiles and conveyor belts. The envelope curve can be shown on the on-site display for simple diagnosis. Linearization function (up to 32 points) for conversion of the measured value into any unit of length, volume or flow rate.

Endress+Hauser (E+H) Ultrasonic Level Sensor FMU42

Benefits

- Reliable non-contact measurement
- Quick and simple commissioning via menu-guided on-site operation with four-line plain text display, 7 languages selectable
- Envelope curves on the on-site display for simple diagnosis
- Hermetically sealed and potted sensor Endress+Hauser (E+H) Ultrasonic Level Sensor FMU42
- Chemically resistant sensor out of PVDF
- Calibration without filling or discharging
- Integrated temperature sensor for automatic correction of the temperature dependent sound velocity

Endress+Hauser (E+H) Ultrasonic Level Sensor FMU42
Field of application
Two-wire or four wire instrument for continuous non-contact level and flow measurement.
- Process connection: Flange
- Temperature: -40 to +80°C (-40 to +176°F)
- Pressure: +0.7 to +2.5bar (+10 to +36psi)
- Maximum measuring distance: Liquids 10m (33ft), Solids 5m (16ft)
- Blocking distance: Liquids and Solids 0.4m (1.3ft)
- International explosion protection certificates