This module performs as the PROFIBUS-DP master device (referred to as the master device) to communicate and exchange data with PROFIBUS-DP slave devices (*1) (referred to as the slave device).
This PROFIBUS-DP communication module can be mounted on field control units (AFV30 , AFV40 ). It can also be mounted on the ESB bus node unit (ANB10) and the optical ESB bus node unit (ANB11 ) which are connected to AFV30 or AFV40 .
*1: The PROFIBUS-DP slave devices represent the field bus devices connected to a PROFIBUS-DP communication cable.
PROFIBUS remote I/O, PLC, and others are among the PROFIBUS-DP slave devices. HART devices and 4-20 mA analog equipment are connected to PROFIBUS remote I/O. ALP121 module can also be connected with PROFIBUS-PA devices via a PROFIBUS DP/PA coupler and refer to the PROFIBUS-PA device data.
HARDWARE SPECIFICATIONS
Hardware specifications for ALP121 PROFIBUS-DP communication module are as shown below.
PROFIBUS-DP Communication Module Hardware Specifications
Item
|
Specifications
|
Model
|
ALP121
|
Interface
|
PROFIBUS-DP
|
Connection method
|
EIA-RS-485-compliant
|
Signal isolation
|
Isolated between filed and the system
|
Transmission speed
|
9600 bps to 12 Mbps
|
Maximum transmission distance
|
1.2 km per segment (at the communication speed of 9600 bps)
|
Number of communication port
|
One port
|
Communication port
|
D-sub 9 pin (female) (*1)
|
Maximum current consumption
|
0.7 A
|
Weight
|
0.3 kg
|
*1: The cables, connectors, and terminators must comply with PROFIBUS-DP standards (PROFIBUS Specifications IEC61158-2 type3).