Manufacturer: Yokogawa Electric Corporation
Yokogawa Duplexed Field Control Unit A2FV50S
GENERAL
This General Specifications (GS) covers the hardware specifications of a Field Control Unit (FCU) which is the intelligent part of the Field Control Station (FCS).This product supports both N-IO and FIO. However,only the communication module is supported among the I/O modules for FIO.
Yokogawa Duplexed Field Control Unit A2FV50S
STANDARD SPECIFICATIONS
Memory Protection During Power Failure
Battery
Battery Back-up for Main Memory: Max. 72 hours
Battery Recharge Time: Min. 48 hours
READY Contact Output
2 terminals (NC, C)
Contact Points open during FCU failure
Contact Rating: 30 V DC, max. 0.3 A
Control Bus Interface
Vnet/IP Interface: Dual-redundant
For more details, refer to the GS “Integrated Prodction Control Systrm CENTUM VP System Overview” (GS 33J01A10-01EN)
Installation Restrictions for Node Units
An N-IO node can be connected under EC4 1, A2EN40, and ANT4 1 installed in A2FV50 via an N-ESB bus or optical ESB bus.
An FIO node can be connected only under EC4 1 and ANT4 1 installed in A2FV50 via an ESB bus or optical ESB bus.
Module Configuration
Power Supply Module (PW481 or PW482 or PW484): 2 modules for dual-redundant configuration.
Processor Module (CP461 style S2 or later or CP471): 2 modules for dual redundant configuration.
A dual-redundant configuration is enabled by using 2 identical modules with same model code (CP461 or CP471).
I/O Module (*1): Each 2 modules for dual redundant configuration
(*2) and total Max. 8
Power Supply
Voltage: 100-120 V AC, Frequency: 50/60 Hz
Voltage: 220-240 V AC, Frequency: 50/60 Hz
Voltage: 24 V DC
Specify with the Suffix Code.
Power Consumption
100-120 V AC: 200 VA
220-240 V AC: 230 VA
24 V DC: 5.5 A
Weight
Approx. 6.9 kg (A2FV50S)
Approx. 7.7 kg (A2FV50D)
Mounting
19-inch Rack Mounting: Rack mount (M5x8 screws) Insulation bush (accessory)
Connection
Power Supply: M4 screw terminal connection
Grounding: M4 screw terminal connection
READY Contact Output: M4 screw terminal connection
Vnet/IP Interface: Connect UTP cable (CAT5e or better) to Layer 2 switch.
STANDARD ACCESSORIES
Parts Names
|
Parts Numbers
|
Quantity
|
Remarks
|
Insulating bush
|
S9049PM
|
8
|
Accessory
|
Yokogawa Duplexed Field Control Unit A2FV50S
|
|
Description
|
Model
|
A2FV50S
|
Field Control Unit (for N-IO, 19-inch Rack Mountable)
|
Suffix
Codes
|
-A
|
Standard type (for CP471) (*1) (*2)
|
-S
|
Standard type (for CP461) (*3)
|
3
|
Dual-redundant Vnet/IP, single power supply
|
4
|
Dual-redundant Vnet/IP, dual-redundant power supply
|
1
|
Always 1
|
1
|
100 - 120 V AC power supply (*4)
|
2
|
220 - 240 V AC power supply (*4)
|
4
|
24 V DC power supply (*4)
|
0
|
With no explosion protection
|
1
|
With explosion protection
|
0
|
Basic type
|
1
|
With ISA Standard G3 option
|
0
|
Always 0
|
Option
Code
|
/ATDOC
|
Explosion Protection Manual (*5)
|
/MRN
|
With Marine Standards (*2)
|
*1: CP471 runs with CENTUM VP R6.05 or later version of Control Function for Field Control Station. CP471 can be combined with the style code S3 or later of ESB bus coupler module EC401. See GS 33J60E30-01EN.
*2: Select the option code “/MRN” if A2FV50 with marine standards is required. Combination of the suffix code “-A” and the option code is inhibit.
*3: Shipped with CP461. Also CP471 is usable. Replacement from CP461 to CP471 is prohibited to perform by a user.
Replacement work must be done by the service engineer authorized by Yokogawa Electric Corporation. CP471 can be combined with the style code S3 or later of ESB bus coupler module EC401. See GS 33J60E30-01EN.
*4: To meet the safety standards and EMC standards, the unit must be installed in a keyed metallic cabinet.
*5: Select the option code “/ATDOC” to follow the ATEX Directive when any of N-IO components are used for explosion protection.