Product Information

Yokogawa Duplexed Field Control Unit A2FV50S[Product print page]

Product Name: Yokogawa Duplexed Field Control Unit A2FV50S
Product Type: A2FV50S
Exhibitors: Yokogawa
Product Documentation: No Related Documents

Brief

Yokogawa Duplexed Field Control Unit A2FV50S, Yokogawa Duplexed Field Control Unit A2FV50S, Yokogawa Duplexed Field Control Unit A2FV50S


 Detailed description

Manufacturer: Yokogawa Electric Corporation

Yokogawa Duplexed Field Control Unit A2FV50S

GENERAL
This General Specifications (GS) covers the hardware specifications of a Field Control Unit (FCU) which is the intelligent part of the Field Control Station (FCS).This product supports both N-IO and FIO. However,only the communication module is supported among the I/O modules for FIO.

Yokogawa Duplexed Field Control Unit A2FV50S


STANDARD SPECIFICATIONS
Memory Protection During Power Failure
Battery
Battery Back-up for Main Memory:     Max. 72 hours
Battery Recharge Time:                     Min. 48 hours
READY Contact Output
2 terminals (NC, C)
Contact Points open during FCU failure
Contact Rating:       30 V DC, max. 0.3 A

 Control Bus Interface
Vnet/IP Interface:    Dual-redundant
For more details, refer to the GS “Integrated Prodction Control Systrm CENTUM VP System Overview” (GS 33J01A10-01EN)

 Installation Restrictions for Node Units
An N-IO node can be connected under EC4 1, 
A2EN40, and ANT4 1 installed in A2FV50 via an N-ESB bus or optical ESB bus.

An FIO node can be connected only under EC4 1 and ANT4 1 installed in A2FV50 via an ESB bus or optical ESB bus.


Module Configuration
Power Supply Module (PW481 or PW482 or PW484):         2 modules for dual-redundant configuration.
Processor Module (CP461 style S2 or later or CP471):        2 modules for dual redundant configuration.
A dual-redundant configuration is enabled by using 2 identical modules with same model code (CP461 or CP471).
I/O Module (*1): Each 2 modules for dual redundant configuration

                 (*2) and total Max. 8

 Power Supply

Voltage:         100-120 V AC, Frequency: 50/60 Hz
Voltage:         220-240 V AC, Frequency: 50/60 Hz
Voltage:         24 V DC
Specify with the Suffix Code.
 Power Consumption
100-120 V AC:        200 VA
220-240 V AC:        230 VA
24 V DC:                5.5 A
 Weight
Approx. 6.9 kg (A2FV50S)
Approx. 7.7 kg (A2FV50D)
 Mounting
19-inch Rack Mounting:  Rack mount (M5x8 screws)           Insulation bush (accessory)
 Connection
Power Supply:                  M4 screw terminal connection
Grounding:                       M4 screw terminal connection
READY Contact Output:   M4 screw terminal connection
Vnet/IP Interface:             Connect UTP cable (CAT5e or better) to  Layer 2 switch.


STANDARD ACCESSORIES

Parts Names

Parts Numbers

Quantity

Remarks

Insulating bush

S9049PM

8

Accessory


Yokogawa Duplexed Field Control Unit A2FV50S

 

 

Description

Model

A2FV50S

Field Control Unit (for N-IO, 19-inch Rack Mountable)

 

 

 

 

 

 

 

 

Suffix

Codes

-A

Standard type (for CP471) (*1) (*2)

-S

Standard type (for CP461) (*3)

3

Dual-redundant Vnet/IP, single power supply

4

Dual-redundant Vnet/IP, dual-redundant power supply

1

Always 1

1

100 - 120 V AC power supply (*4)

2

220 - 240 V AC power supply (*4)

4

24 V DC power supply (*4)

0

With no explosion protection

1

With explosion protection

0

Basic type

1

With ISA Standard G3 option

0

Always 0

Option

Code

/ATDOC

Explosion Protection Manual (*5)

/MRN

With Marine Standards (*2)

*1: CP471 runs with CENTUM VP R6.05 or later version of Control Function for Field Control Station. CP471 can be combined with the style code S3 or later of ESB bus coupler module EC401. See GS 33J60E30-01EN.
*2: Select the option code “/MRN” if A2FV50 with marine standards is required. Combination of the suffix code “-A” and the option code is inhibit.
*3: Shipped with CP461. Also CP471 is usable. Replacement from CP461 to CP471 is prohibited to perform by a user.
Replacement work must be done by the service engineer authorized by Yokogawa Electric Corporation. CP471 can be combined with the style code S3 or later of ESB bus coupler module EC401. See GS 33J60E30-01EN.
*4: To meet the safety standards and EMC standards, the unit must be installed in a keyed metallic cabinet.
*5: Select the option code “/ATDOC” to follow the ATEX Directive when any of N-IO components are used for explosion protection.