Product Name: Yokogawa Digital Indicator UM330-00
Product Type: UM330-00
Exhibitors: Yokogawa
Product Documentation: No Related Documents

Brief

Yokogawa Digital Indicator UM330-00 employ an easy-to-read, 14-segment large color LCD display. Yokogawa Digital Indicator UM330-00,dedicated LL50A Parameter Setting Software. UM330 was discontinued, replaced by UM33A series.


 Detailed description

Yokogawa Digital Indicator UM330-00


UM330 was discontinued, replaced by UM33A series. 

 Features

Yokogawa Digital Indicator UM330-00

   A 14-segment, active (PV display color changing function) color LCD display is employed.

Two five-digit, high-resolution displays are possible. Alphabet letters can be displayed in an easy-to-read manner. The guide display shows parameter names. 

• Easy to operate

Navigation keys (SET/ENTER and Up/Down/Left/ Right arrow keys)are employed to facilitate making settings.

• 65 mm depth

The small depth enables the mounting in a thin and small instrumented panel.


Construction, Installation, and Wiring

Yokogawa Digital Indicator UM330-00

• Dust-proof and drip-proof: IP66 (for front panel)

• Material: Polycarbonate (Flame retardancy: UL94V-0)

• Case color: White (Light gray) or Black (Light

Charcoal gray)

• Weight: 0.5 kg or less

• External dimensions (mm): 96 (W) × 48 (H) × 65 (depth from the panel face)

(Depth except the projection on the rear panel)

• Installation: Direct panel mounting; mounting bracket, one each for left and right mounting

• Panel cutout dimensions (mm): 92+0.8/0  (W) × 45+0.6/0

(H)

• Mounting attitude: Up to 30 degrees above the horizontal. No downward titling allowed.

• Wiring: M3 screw terminal with square washer (for signal wiring and power wiring)


Power Supply Specifications and Isolation

Yokogawa Digital Indicator UM330-00

• Power supply:
Rated voltage:100 – 240 V AC (+10%/-15%), 50/60 Hz
24 V AC/DC (+10%/-15%) (for /DC option)
• Power consumption: 15 VA (DC: 7 VA, AC: 11 VA if
/DC option is specified)
• Data backup: Nonvolatile memory
• Power holdup time: 20 ms (for 100 V AC drive)
• Withstanding voltage
- Between primary terminals and secondary terminals: 2300 V AC for 1 minute (UL, CSA)
- Between primary terminals and secondary terminals: 3000 V AC for 1 minute (CE)
- Between primary terminals: 1500 V AC for 1 minute
- Between secondary terminals: 500 V AC for 1 minute
(Primary terminals: Power (*) and relay output
terminals; Secondary terminals: Analog I/O signal terminals, contact input terminals, communication terminals, and functional grounding terminals.)
(*): Power terminals for 24V AC/DC models are the secondary terminals.
• Insulation resistance
Between power supply terminals and a grounding terminal: 20 MΩ or more at 500 V DC


Environmental Conditions

Normal Operating Conditions

Yokogawa Digital Indicator UM330-00
• Ambient temperature: -10 to 50ºC
• Ambient humidity: 20 to 90% RH (no condensation allowed)
• Magnetic field: 400 A/m or less
• Continuous vibration at 5 to 9 Hz: Half amplitude of
1.5 mm or less, 1oct/min for 90 minutes each in the three axis directions
Continuous vibration at 9 to 150 Hz: 4.9 m/s2 or less, 1oct/min for 90 minutes each in the three axis directions
• Short-period vibration: 14.7 m/s2, 15 seconds or less
• Shock: 98 m/s2 or less, 11 ms
• Altitude: 2000 m or less above sea level
• Warm-up time: 30 minutes or more after the power is turned on
• Startup time: Within 10 seconds

*: The LCD (a liquid crystal display) is used for a display portion of this product.
The LCD has a characteristic that the display action becomes late at the low temperature.