Hardware Specifications
Processor
VR5532 (350 MHz)
Main Memory Capacity
128 Mbyte
Memory Protection During Power Failure
Battery
Battery Back-up for Main Memory: Max. 72 hours
Battery Recharge Time: Min. 48 hours
FCU Status Contact Output
3 terminals (NC, NO and C) Contact Points open or close during FCU failure Contact Rating: Rated voltage: 250 V AC, max. 30 V DC Rated current: Max. 2 A Rated power supply: Max. 125 VA
Communication Interface
Vnet/IP Interface: Dual-redundant ESB Bus Interface: Dual-redundant or single (Always dual-redundant for AFV40D)
House Keeping (HK) Function A House Keeping Unit (HKU) is standard hardware component provided with the type of FCU. With the HK function is able to monitor the environmental conditions of the connected cabinets via HK bus and/or optical ESB bus, and display HKU’s operating status on HIS. System alarms can also be displayed. Cable: HK Bus cable (AKBHKU) Units that can be connected HKU of AFV40S, AFV40D: HKU of ACUKT1, ACUKT2, ACB51, or XLCabinet. Maximum number of connectable cabinets: 9/FCU(AFV40S, AFV40D) Total maximum length of cable: 100 m
Weight
Approx. 240kg (excluding node) Approx. 360 kg (at max. node installation)
Contact Number: +86 13724889019 Email: tekrachel2024@163.com Web: www.tek-international.com WeChat: tekrachel