Brand: Yokogawa. Manufacturer: Yokogawa Electric Corporation
STARDOM: FCN, FCN-500, FCN-100, FCN-RTU, FCJ
Yokogawa Base Module NFBU050-S15
Features
• High-performance, high-reliability modular controller • Memory with ECC • Low heat dissipation eliminates the need for a fan • A wealth of RAS features -CPU self-diagnostics, temperature monitoring, I/O diagnostics, and more • The CPU, power supply module, local bus (SB bus), and control network can all be duplexed, and all modules are hot-swappable. • Can function as link active schedulers (LASs) for low-speed voltage mode (H1) FOUNDATION Fieldbus segments, and link up FOUNDATION Fieldbus-enabled field devices.
Configuration
An FCN-100 consists of the following: • Base module • Power supply module • CPU module • SB bus repeat module (extending the SB bus, the local bus for FCNs, to connect an extension unit) • I/O modules There are two types of base module. - NFBU200 base module (long): Up to 2 extension units connectable for I/O expansion - NFBU050 base module (short): Compact and dedicated to one-unit-configuration
Maximum I/O Module Configurations
Base Module Unit Configuration Standard Duplexed (*1) NFBU200 base module (long) Control unit only Max. 8 modules Max. 6 modules With 1 extension unit Max. 16 modules Max. 12 modules With 2 extension unit Max. 25 modules Max. 20 modules NFBU050 base module (short) Control unit (*2) Max. 3 modules Not applicable (*3) *1: When CPU and SB bus repeat modules are duplexed *2: SB bus repeat modules cannot be mounted on NFBU050. *3: Neither power supply nor CPU modules can be duplexed on NFBU050.
Base Module
Unit Configuration
Standard
Duplexed (*1)
NFBU200 base module (long)
Control unit only
Max. 8 modules
Max. 6 modules
With 1 extension unit
Max. 16 modules
Max. 12 modules
With 2 extension unit
Max. 25 modules
Max. 20 modules
NFBU050 base module (short)
Control unit (*2)
Max. 3 modules
Not applicable (*3)
Installation Requirements
Item
Specification
Ambient temperature
Operation
0° to 55°C
Transportation/storage
– 40° to 85°C (*1)
Ambient humidity
5 to 95 %RH (no condensation)
Rate of change in temperature
Within ±10°C/h
Within ±20°C/h
Dust
0.3 mg/m3 or less
Protection class
IP20
Resistance to corrosive gases
ANSI/ISA S71.04 Class G2 (Standard) (ANSI/ISA S71.04 Class G3, option)
Resistance to vibration
0.15 mm P-P (5 to 58 Hz), 1 G (58 to 150 Hz)
Resistance to shock
15 G, 11 ms (during power-off, for sine half-waves in XYZ-directions)
Altitude
2000 m or less
Noise
Electric field
3 V/m or less (26 MHz to 1 GHz)
Magnetic field
30 A/m (AC) or less, 400 A/m (DC) or less
Electrostatic discharge
4 kV or less contact discharge, 8 kV or less aerial discharge
Grounding
Apply the grounding system which is defined by the rules and standards of the country or the region.
Cooling
Natural air cooling
Model and Suffix Codes
Base Module (long)
Description
Model
NFBU200
Base module (long)
Suffix Codes
-S
Standard type
0
19-inch rack-mounted
1
DIN rail-mounted
5
Basic type with no explosion protection
6
With ISA Standard G3 option and no explosion protection
E
Basic type with explosion protection
F
With ISA Standard G3 option and explosion protection
Base Module (short)
NFBU050
Base module (short)
Optional Accessories
NFDCV01
Dummy cover for I/O module slot
NFDCV02
Dummy cover for power supply module slot
NFBU200-S0£
NFBU200-S1£
NFBU050-S1£
Weight
1.9 kg
1.0 kg
0.58 kg
Dimensions (W x H x D)
482.6Í132.5Í40.5 mm
440Í131Í42.3 mm
283Í131Í24.2 mm
Mounting
Maximum power consumption
5 V
Self-consumption
0.4 A(max)
0.025 A
24 V
Contact Number: +86 13724889019 Email: tekrachel2024@163.com Web: www.tek-international.com WeChat: tekrachel tekrachel@163.com