Brand: Yokogawa. Manufacturer: Yokogawa Electric Corporation
STARDOM: FCN, FCN-500, FCN-100, FCN-RTU, FCJ
Yokogawa FCN Autonomous Controller Hardware
Features
Yokogawa FCN Autonomous Controller Hardware
• High-performance, high-reliability modular controller
• Memory with ECC
• Low heat dissipation eliminates the need for a fan
• A wealth of RAS features -CPU self-diagnostics, temperature monitoring, I/O diagnostics, and more
• The CPU, power supply module, local bus (SB bus), and control network can all be duplexed, and all modules are hot-swappable.
• Can function as link active schedulers (LASs) for low-speed voltage mode (H1) FOUNDATION Fieldbus segments, and link up FOUNDATION Fieldbus-enabled field devices.
Configuration
Yokogawa FCN Autonomous Controller Hardware
An FCN-100 consists of the following:
• Base module
• Power supply module
• CPU module
• SB bus repeat module (extending the SB bus, the local bus for FCNs, to connect an extension unit)
• I/O modules
There are two types of base module.
- NFBU200 base module (long): Up to 2 extension units connectable for I/O expansion
- NFBU050 base module (short): Compact and dedicated to one-unit-configuration
Maximum I/O Module Configurations
Base Module
|
Unit Configuration
|
Standard
|
Duplexed (*1)
|
NFBU200 base module (long)
|
Control unit only
|
Max. 8 modules
|
Max. 6 modules
|
With 1 extension unit
|
Max. 16 modules
|
Max. 12 modules
|
With 2 extension unit
|
Max. 25 modules
|
Max. 20 modules
|
NFBU050 base module (short)
|
Control unit (*2)
|
Max. 3 modules
|
Not applicable (*3)
|
*1: When CPU and SB bus repeat modules are duplexed
*2: SB bus repeat modules cannot be mounted on NFBU050.
*3: Neither power supply nor CPU modules can be duplexed on NFBU050.
Installation Requirements
Yokogawa FCN Autonomous Controller Hardware
Item
|
Specification
|
Ambient temperature
|
Operation
|
0° to 55°C
|
Transportation/storage
|
– 40° to 85°C (*1)
|
Ambient humidity
|
Operation
|
5 to 95 %RH (no condensation)
|
Transportation/storage
|
5 to 95 %RH (no condensation)
|
Rate of change in
temperature
|
Operation
|
Within ±10°C/h
|
Transportation/storage
|
Within ±20°C/h
|
Dust
|
0.3 mg/m3 or less
|
Protection class
|
IP20
|
Resistance to corrosive gases
|
ANSI/ISA S71.04 Class G2 (Standard) (ANSI/ISA S71.04 Class G3, option)
|
Resistance to vibration
|
0.15 mm P-P (5 to 58 Hz), 1 G (58 to 150 Hz)
|
Resistance to shock
|
15 G, 11 ms (during power-off, for sine half-waves in XYZ-directions)
|
Altitude
|
2000 m or less
|
Noise
|
Electric field
|
3 V/m or less (26 MHz to 1 GHz)
|
Magnetic field
|
30 A/m (AC) or less, 400 A/m (DC) or less
|
Electrostatic discharge
|
4 kV or less contact discharge, 8 kV or less aerial discharge
|
Grounding
|
Apply the grounding system which is defined by the rules and standards of the
country or the region.
|
Cooling
|
Natural air cooling
|
*1: System clock may be reset if the temperature falls below -10°C.
Base Module
NFBU200
NFBU050
NFDCV01
NFDCV02
Power Supply Module
NFPW441
NFPW442
NFPW444
CPU Module
NFCP100
SB Bus Repeat Module
NFSB10
NFSBT01
NFSBT02
NFCB301
I/O Module
Yokogawa FCN Autonomous Controller Hardware
An autonomous controller FCN supports versatile I/O modules.
List of FCN’s Modules and Modules Conforming to Explosion Protection Standards
Table List of FCN’s Modules and Modules Conforming to Explosion Protection Standards (1/2)
Type
|
Model
|
Function
|
Explosion protection
|
FM NI (Non- incen-
dive)
|
ATEX Type “n”
|
CSA NI (Non- Incen-
dive)
|
Base module
|
NFBU200
|
Base module (long)
|
X
|
X
|
X
|
NFBU050
|
Base module (short)
|
X
|
X
|
X
|
Power supply module
|
NFPW441
|
Power supply module (100 - 120 V AC input)
|
X
|
–
|
X
|
NFPW442
|
Power supply module (220 - 240 V AC input)
|
–
|
–
|
–
|
NFPW444
|
Power supply module (24 V DC input)
|
X
|
X
|
X
|
CPU module
|
NFCP100
|
CPU module for FCN
|
X
|
X
|
X
|
SB bus repeat
module
|
NFSB100
|
SB bus repeat module for FCN
|
X
|
X
|
X
|
Analog I/O Modules (*1)
|
NFAI141
|
Analog Input Module (4 to 20 mA, 16-channel, Non-Isolated)
|
XX (*2)
|
X
|
XX (*2)
|
NFAV141
|
Analog Input Module (1 to 5 V: differential input, 16-channel, Non-
Isolated)
|
X
|
X
|
X
|
NFAV142
|
Analog Input Module (-10 to +10 V, 16-channel, Non-Isolated)
|
X
|
X
|
X
|
NFAI841
|
Analog I/O Module (4 to 20 mA input, 4 to 20 mA output, 8-channel input/8-channel output, Non-Isolated)
|
XX (*2)
|
X
|
XX (*2)
|
NFAB841
|
Analog I/O Module (1 to 5 V input: differential input, 4 to 20 mA output, 8-channel input/8-channel output, Non-Isolated)
|
X
|
X
|
X
|
NFAV542
|
Analog Output Module (-10 to +10 V, 16-channel, Non-Isolated)
|
X
|
X
|
X
|
NFAI143
|
Analog Input Module (4 to 20 mA, 16-channel, Isolated)
|
X
|
X
|
X
|
NFAI543
|
Analog Output Module (4 to 20 mA, 16-channel, Isolated)
|
X
|
X
|
X
|
NFAV144
|
Analog Input Module (-10 to +10 V, 16-channel, Isolated)
|
X
|
X
|
X
|
NFAV544
|
Analog Output Module (-10 to +10 V, 16-channel, Isolated)
|
X
|
X
|
X
|
NFAT141
|
TC/mV Input Module (16-channel, Isolated)
|
X
|
X
|
X
|
NFAR181
|
RTD Input Module (12-channel, Isolated)
|
X
|
X
|
X
|
NFAI135
|
Analog Input Module (4 to 20 mA, 8-channel, Isolated channels)
|
X
|
X
|
X
|
NFAI835
|
Analog I/O Module (4 to 20 mA, 4-channel input/4-channel output,
Isolated channels)
|
X
|
X
|
X
|
NFAP135
|
Pulse Input Module (8-channel, Pulse count, 0 to 10 kHz, Isolated channels)
|
X
|
X
|
X
|
NFAF135
|
Frequency Input Module (8-channel, 0.1 Hz to 10 kHz, Isolated
channels)
|
X
|
X
|
X
|
Digital I/O Modules
(*1)
|
NFDV151
|
Digital Input Module (32-channel, 24 V DC, Isolated)
|
X
|
X
|
X
|
NFDV157
|
Digital Input Module (32-channel, 24 V DC, Pressure Clamp Terminal support only, Isolated)
|
X
|
X
|
X
|
NFDV161
|
Digital Input Module (64-channel, 24 V DC)
|
–
|
–
|
–
|
NFDV141
|
Digital Input Module (16-channel, 100 V - 120 V AC, Isolated)
|
X
|
–
|
X
|
NFDV142
|
Digital Input Module (16-channel, 200 - 240 V AC)
|
–
|
–
|
–
|
X: Conforming
XX: Conforming conditionally
N.A.: Not applicable
*1: To use modules as hazardous location equipment (non-incendive), use the specified pressure-clamp terminal blocks or MIL
connector cables (KMS40, KMS50) / MIL connector terminal blocks (TAS40 and TAS50) .
*2: I/O modules with suffix code “with HART communication” do not conform to the explosion-proof standards.
Table List of FCN’s Modules and Modules Conforming to Explosion Protection Standards (2/2)
Type
|
Model
|
Function
|
Explosion protection
|
FM NI (Non- incen-
dive)
|
ATEX Type “n”
|
CSA NI (Non- Incen-
dive)
|
Digital I/O Modules
(*1)
|
NFDV532
|
Pulse Width Output Module (4-channel : Up Pulse/Down Pulse, 24 V DC, Isolated)
|
–
|
–
|
–
|
NFDV551
|
Digital Output Module (32-channel, 24 V DC, Isolated)
|
X
|
X
|
X
|
NFDV557
|
Digital Output Module (32-channel, 24 V DC, Pressure Clamp Terminal support only, Isolated)
|
X
|
X
|
X
|
NFDV561
|
Digital Output Module (64-channel, 24 V DC)
|
–
|
–
|
–
|
NFDR541
|
Relay Output Module (16-channel, 24 to 110 V DC/100 to 240 V AC, Isolated)
|
XX (*3)
|
XX (*4)
|
XX (*3)
|
Turbomachinery
I/O Module(*5)
|
NFGS813
|
Servo Module
|
–
|
–
|
–
|
NFGP813
|
High Speed Protection Module
|
–
|
–
|
–
|
Communication
Modules
|
NFLC121
|
CANopen Communication Module(1-port, 10 kbps to 1 Mbps)
|
–
|
–
|
–
|
NFLF111
|
Foundation fieldbus communication module (4-port)
|
X
|
X
|
X
|
NFLP121
|
PROFIBUS-DP Communication Module (1-port, 9.6 kbps to 12 Mbps)
|
–
|
–
|
–
|
NFLR111
|
RS-232-C Communication Module (2-port, 300 bps to 115.2 kbps)
|
X
|
X
|
X
|
NFLR121
|
RS-422/RS-485 Communication Module (2-port, 300 bps to 115.2 kbps)
|
X
|
X
|
X
|
Pressure Clamp
Terminal Block
|
NFTA4S
|
Pressure Clamp Terminal Block for Analog (16-channel)
|
X
|
X
|
X
|
NFTT4S
|
Pressure Clamp Terminal Block for Thermocouple/mV
(16-channel)
|
X
|
X
|
X
|
NFTR8S
|
Pressure Clamp Terminal Block for RTD (12-channel)
|
X
|
X
|
X
|
NFTB5S
|
Pressure Clamp Terminal Block for Digital Input (32-channel)
|
X
|
X
|
X
|
NFTD5S
|
Pressure Clamp Terminal Block for Digital Output (32-channel)
|
X
|
X
|
X
|
NFTI3S
|
Pressure Clamp Terminal Block for Isolated Analog Module and Pulse Module (for NFAI135, NFAP135, NFAF135: 8-channel, NFAI835: 4-channel input, 4-channel output)
|
X
|
X
|
X
|
NFTC4S
|
Pressure Clamp Terminal Block for Digital (16-channel, with dedicated
connector, without surge absorber)
|
X
|
X
|
X
|
NFTC5S
|
Pressure Clamp Terminal Block for Digital (32-channel, with dedicated
connector)
|
X
|
X
|
X
|
NFTF9S
|
Pressure Clamp Terminal Block for Foundation Fieldbus
|
X
|
X
|
X
|
Terminal Block
|
TAS40
|
MIL Connector Terminal Block (40 Pole Plug Types, M3.5)
|
X
|
X
|
X
|
TAS50
|
MIL Connector Terminal Block (50 Pole Plug Types, M3.5)
|
X
|
X
|
X
|
Cable
|
NFCB301
|
SB Bus Cable
|
X
|
X
|
X
|
KMS40
|
MIL Connector Cable (40 Pole Plug Types)
|
X
|
X
|
X
|
KMS50
|
MIL Connector Cable (50 Pole Plug Types)
|
X
|
X
|
X
|
SB Bus T-joint
|
NFSBT01
|
SB Bus T-joint
|
X
|
X
|
X
|
NFSBT02
|
SB Bus T-joint with Built-in Terminator
|
X
|
X
|
X
|
Dummy Cover
|
NFDCV01
|
Dummy Cover for I/O Module Slot
|
N.A.
|
N.A.
|
N.A.
|
NFDCV02
|
Dummy Cover for Power supply Module Slot
|
N.A.
|
N.A.
|
N.A.
|
NFCCC01
|
MIL Cable Connector Cover
|
N.A.
|
N.A.
|
N.A.
|
X: Conforming
XX: Conforming conditionally
N.A.: Not applicable
*1: To use modules as hazardous location equipment (non-incendive), use the specified pressure-clamp terminal blocks or MIL
connector cables (KMS40, KMS50) / MIL connector terminal blocks (TAS40 and TAS50) .
*2: I/O modules with suffix code “with HART communication” do not conform to the explosion-proof standards.
*3: The relay output module (NFDR541) does not conform to the explosion-proof standards when it is used in between 100 to
240V AC..
*4: The relay output module (NFDR541) is compliant with the standards only when the voltage of 24 VDC or less is applied to its output terminal.
*5: For Turbomachinery I/O Modules, refer to GS 34P02Q04-01E Turbomachinery Controller Overview.