Product Information

Yokogawa Relay Output Module NFDR541[Product print page]

Product Name: Yokogawa Relay Output Module NFDR541
Product Type: NFDR541
Exhibitors: Yokogawa
Product Documentation: No Related Documents

Brief

Yokogawa Relay Output Module NFDR541, Yokogawa Relay Output Module NFDR541, 16-channel, 24 to 110 V DC/100 to 240 V AC, Isolated.


 Detailed description

Brand: Yokogawa.  Manufacturer: Yokogawa Electric Corporation

STARDOMFCN, FCN-500, FCN-100, FCN-RTU, FCJ

Yokogawa Relay Output Module NFDR541

Standard Specifications

Relay Output Module
The Relay Output Module outputs the 16-channel relay contact signals.

Yokogawa Relay Output Module NFDR541

Item

Specifications

Model

NFDR541

Number of output channels

16

Rated applied voltage (*1)

24 to 110 V DC, 100 to 240 V AC, 50/60Hz

 

 

Maximum load current (*2)

Resistive load:

24 V DC: 2.0 A/channel, 48V DC: 1.0A/channel,110 V DC: 0.4 A/channel

100 V AC: 2.0 A/channel, 220 V AC: 2.0 A/channel

Inductive load:

24 V DC: 0.6 A/channel, 48V DC: 0.3A/channel,110 V DC: 0.1 A/channel

100 V AC: 1.0 A/channel, 220 V AC: 1.0 A/channel

 

Withstanding voltage

Between output signal and system: 2 kV AC

Between commons: 1.35 kV AC, common every 8-channel

Functions

Status output

 

ON/OFF status output function

 

Output fallback (*3) (*4)

HOLD: Holds the current states when the fallback action is triggered.

OFF: Resets all the output channels to off when the fallback action is triggered. NO: Performs no fallback action.

Output response time

12 ms or less (for status output)

Maximum current consumption

780 mA (5 V DC)

Weight

0.3 kg

External connection

Pressure clamp terminal

*1: NFDR541 is compliant with the EU Directives only when the voltage of 53 VDC or less is applied to its output terminal.
*2: Maximum 8 A is allowed per common. Connect a spark killer diode when driving DC relay. Yokogawa Relay Output Module NFDR541
*3: Fallback detection time is 4 seconds. 
*4: HOLD, OFF, or NO should be chosen for all channels commonly. Yokogawa Relay Output Module NFDR541
Note: The signals connected the same common should be the same phase when applying AC voltage.

Models and Suffix Codes 

Digital Output Module

Yokogawa Relay Output Module NFDR541

 

 

Description

Model

NFDR541

Relay Output Module (16-channel, 24 to 110 V DC/100 to 240 V AC, Isolated)

 

 

Suffix Codes

-P

Standard type

5

General-purpose type with no explosion protection

E

General-purpose type with explosion protection

0

Basic type

1

With ISA Standard G3 option

Option Code

/C4S70

With Pressure Clamp Terminal Block for Digital Input [Model : NFTC4S-70]