Product Information

Yokogawa Digital Output Module NFDV561[Product print page]

Product Name: Yokogawa Digital Output Module NFDV561
Product Type: NFDV561
Exhibitors: Yokogawa
Product Documentation: No Related Documents

Brief

Yokogawa Digital Output Module NFDV561, Yokogawa Digital Output Module NFDV561, 64-channel, 24V DC, Isolated.


 Detailed description

Brand: Yokogawa.  Manufacturer: Yokogawa Electric Corporation

STARDOMFCN, FCN-500, FCN-100, FCN-RTU, FCJ

Yokogawa Digital Output Module NFDV561

Standard Specifications

Digital Output Modules
The Digital Output Modules output 32-channel or 64-channel transistor contact signals.

Yokogawa Digital Output Module NFDV561

Item

Specifications

Model

NFDV551

NFDV557

NFDV561

Number of output channels

32

32

64

Rated applied voltage

24 V DC

24 V DC

24 V DC

Load voltage (*1)

24 V DC, 50 mA

24 V DC, 50 mA

24 V DC, 100 mA

Field power supply voltage range

 

20.4 to 26.4 V

 

20.4 to 26.4 V

 

20.4 to 26.4 V

Output ON voltage maximum value

 

2 V DC

 

2 V DC

 

2 V DC

Leak current maximum value when output OFF

 

0.1 mA

 

0.1 mA

 

0.1 mA

Output format

Current sink

Current sink

Current sink

Maximum load current (*2)

100 mA/channel, 26.4 V

100 mA/channel, 26.4 V

100 mA/channel, 26.4 V

 

Withstanding voltage

Between output signal and system: 2 kV AC (*5)

Between commons: 500 V AC, common minus (–) side every 16-channel

Functions

Status output

 

ON/OFF status output function

 

ON/OFF status output function

 

ON/OFF status output function

 

Output fallback (*3) (*4)

HOLD: Holds the current states when the fallback action is triggered.

OFF: Resets all the output channels to off when the fallback action is triggered. NO: Performs no fallback action.

Output response time

3 ms or less (for status output)

 

Maximum current consumption

700 mA (5 V DC)

60 mA (24 V DC, field power

supply)

550 mA (5 V DC)

60 mA (24 V DC, field power

supply)

780 mA (5 V DC)

120 mA (24 V DC, field power

supply)

Weight

0.2 kg

0.3 kg

0.3 kg

 

External connection

Pressure clamp terminal, MIL

connector cable (*5)

 

Pressure clamp terminal

 

MIL connector cable (*5)

*1: An external field power supply (24 V DC) is required for each module. 
*2: Connect a spark killer diode when driving DC relay. Yokogawa Digital Output Module NFDV561
*3: The fallback detection time is 4 seconds. 
*4: HOLD, OFF, or NO should be chosen for all channels commonly. Yokogawa Digital Output Module NFDV561
*5: The withstanding voltage for using MIL connector cable depends on the electrical specifications of its cable.

Models and Suffix Codes 

Digital Output Module

Yokogawa Digital Output Module NFDV561

 

 

Description

Model

NFDV561

Digital Output Module (64-channel, 24V DC, Isolated)

 

 

Suffix Codes

-P

Standard type

5

General-purpose type with no explosion protection

0

Basic type

1

With ISA Standard G3 option