Product Information

Yokogawa Digital Output Module NFDV551-P11[Product print page]

Product Name: Yokogawa Digital Output Module NFDV551-P11
Product Type: NFDV551-P11
Exhibitors: Yokogawa
Product Documentation: No Related Documents

Brief

Yokogawa Digital Output Module NFDV551-P11, Yokogawa Digital Output Module NFDV551-P11, 32-channel, 24 V DC, Isolated.


 Detailed description

Brand: Yokogawa.  Manufacturer: Yokogawa Electric Corporation

STARDOMFCN, FCN-500, FCN-100, FCN-RTU, FCJ

Yokogawa Digital Output Module NFDV551-P11

Standard Specifications

Digital Output Modules
The Digital Output Modules output 32-channel or 64-channel transistor contact signals.

Yokogawa Digital Output Module NFDV551-P11

Item

Specifications

Model

NFDV551

NFDV557

NFDV561

Number of output channels

32

32

64

Rated applied voltage

24 V DC

24 V DC

24 V DC

Load voltage (*1)

24 V DC, 50 mA

24 V DC, 50 mA

24 V DC, 100 mA

Field power supply voltage range

 

20.4 to 26.4 V

 

20.4 to 26.4 V

 

20.4 to 26.4 V

Output ON voltage maximum value

 

2 V DC

 

2 V DC

 

2 V DC

Leak current maximum value when output OFF

 

0.1 mA

 

0.1 mA

 

0.1 mA

Output format

Current sink

Current sink

Current sink

Maximum load current (*2)

100 mA/channel, 26.4 V

100 mA/channel, 26.4 V

100 mA/channel, 26.4 V

 

Withstanding voltage

Between output signal and system: 2 kV AC (*5)

Between commons: 500 V AC, common minus (–) side every 16-channel

Functions

Status output

 

ON/OFF status output function

 

ON/OFF status output function

 

ON/OFF status output function

 

Output fallback (*3) (*4)

HOLD: Holds the current states when the fallback action is triggered.

OFF: Resets all the output channels to off when the fallback action is triggered. NO: Performs no fallback action.

Output response time

3 ms or less (for status output)

 

Maximum current consumption

700 mA (5 V DC)

60 mA (24 V DC, field power

supply)

550 mA (5 V DC)

60 mA (24 V DC, field power

supply)

780 mA (5 V DC)

120 mA (24 V DC, field power

supply)

Weight

0.2 kg

0.3 kg

0.3 kg

 

External connection

Pressure clamp terminal, MIL

connector cable (*5)

 

Pressure clamp terminal

 

MIL connector cable (*5)

*1: An external field power supply (24 V DC) is required for each module. 
*2: Connect a spark killer diode when driving DC relay. Yokogawa Digital Output Module NFDV551-P11
*3: The fallback detection time is 4 seconds. 
*4: HOLD, OFF, or NO should be chosen for all channels commonly. Yokogawa Digital Output Module NFDV551-P11
*5: The withstanding voltage for using MIL connector cable depends on the electrical specifications of its cable.

Models and Suffix Codes 

Digital Output Module

Yokogawa Digital Output Module NFDV551-P11

 

 

Description

Model

NFDV551

Digital Output Module (32-channel, 24 V DC, Isolated)

 

 

Suffix Codes

-P

Standard type

6

With status display and no explosion protection

F

With status display and explosion protection

0

Basic type

1

With ISA Standard G3 option

 

Option Codes

/D5S00

With Pressure Clamp Terminal Block for Digital Output [Model : NFTD5S-00]

/D5S10

With Pressure Clamp Terminal Block for Digital Output (surge absorber) [Model : NFTD5S-10]

/CCC01

With Connector Cover for MIL Cable [Model : NFCCC01]