Brand: Yokogawa. Manufacturer: Yokogawa Electric Corporation
STARDOM: FCN, FCN-500, FCN-100, FCN-RTU, FCJ
Yokogawa Pulse Width Output Module NFDV532-P10
Standard Specifications
Pulse Width Output Module The Pulse Width Output Module outputs 4-channel pulse signals.
Model NFDV532 Number of output channels 4-channel : Up Pulse/Down Pulse Rated applied voltage 24 V DC Load voltage (*1) 24 V DC, 25 mA Field power supply voltage range 20.4 to 26.4 V DC Output ON voltage maximum value 2 V DC Leak current maximum value when output OFF 0.1 mA Output format Current sink Maximum load current (*2) 100 mA/1channel, 26.4 V Withstanding voltage Between output signal and system : 2 kV AC (*5) Output fallback (*3) (*4) HOLD : Reset all the output channels after outputting all pulse signals when a fallback is detected. OFF : Resets all the output channels immediately to off when the fallback action is triggered. NO : Performs no fallback action. Pulse output accuracy 2 ms Min., 2 ms increments (error: 1 ms Max.) Maximum current consumption 550 mA (5 V DC) 25 mA (24 V DC, field power supply) Weight 0.2 kg External connection Pressure clamp terminal, MIL connector cable (*5) *1: An external field power supply (24 V DC) is required for each module. Yokogawa Pulse Width Output Module NFDV532-P10 *2: Connect a spark killer diode when driving DC relay. *3: The fallback detection time is 4 seconds. Yokogawa Pulse Width Output Module NFDV532-P10 *4: HOLD, OFF, or NO should be chosen for all channels commonly. *5: The withstanding voltage for using MIL connector cable depends on the electrical specifications of its cable.
Model
NFDV532
Number of output channels
4-channel : Up Pulse/Down Pulse
Rated applied voltage
24 V DC
Load voltage (*1)
24 V DC, 25 mA
Field power supply voltage range
20.4 to 26.4 V DC
Output ON voltage maximum value
2 V DC
Leak current maximum value when output OFF
0.1 mA
Output format
Current sink
Maximum load current (*2)
100 mA/1channel, 26.4 V
Withstanding voltage
Between output signal and system : 2 kV AC (*5)
Output fallback (*3) (*4)
HOLD : Reset all the output channels after outputting all pulse signals when a fallback is detected.
OFF : Resets all the output channels immediately to off when the fallback action is triggered.
NO : Performs no fallback action.
Pulse output accuracy
2 ms Min., 2 ms increments (error: 1 ms Max.)
Maximum current consumption
550 mA (5 V DC)
25 mA (24 V DC, field power supply)
Weight
0.2 kg
External connection
Pressure clamp terminal, MIL connector cable (*5)
Models and Suffix Codes
Digital Output Module
Description Model NFDV532 Pulse Width Output Module ( 4-channel : Up Pulse/Down Pulse, 24 V DC, Isolated) Suffix Codes -P Standard type 1 With status display 0 Basic type 1 With ISA Standard G3 option Option Codes /D5S00 With Pressure Clamp Terminal Block for Digital Output [Model : NFTD5S-00] /D5S10 With Pressure Clamp Terminal Block for Digital Output (surge absorber) [Model : NFTD5S-10] /CCC01 With Connector Cover for MIL Cable [Model : NFCCC01]
Description
Pulse Width Output Module ( 4-channel : Up Pulse/Down Pulse, 24 V DC, Isolated)
Suffix Codes
-P
Standard type
1
With status display
0
Basic type
With ISA Standard G3 option
Option Codes
/D5S00
With Pressure Clamp Terminal Block for Digital Output [Model : NFTD5S-00]
/D5S10
With Pressure Clamp Terminal Block for Digital Output (surge absorber) [Model : NFTD5S-10]
/CCC01
With Connector Cover for MIL Cable [Model : NFCCC01]