AC Digital Input Modules The AC Digital Input Modules receive 16-channel 100 V AC or 220 V AC ON/OFF signals.
Item Specifications Model NFDV141 NFDV142 Number of input channels 16 16 Rated input voltage (*1) 100 to 120 V AC, 50/60 Hz 200 to 240 V AC, 50/60 Hz Input ON voltage (peak value) 80 V AC (113 V) to 132 V AC (187 V) 160 V AC (226 V) to 264 V AC (373 V) Input OFF voltage (peak value) 20 V AC (28 V) or less 40 V AC (56 V) or less Input current (TYP) 4.7 mA (@120 V/60 Hz) / channel 6.2 mA (@240 V/60 Hz) / channel Input current (MAX) 7 mA / channel 9.3 mA / channel Withstanding voltage Between input signal and system: 2 kV AC Between commons: 1.35 kV AC, common every 8-channel Functions Status input Push button input Function for detecting ON/OFF status Function for counting the push button edge Input response time 160 ms or less (for status input) Minimum ON detection time 200 ms (for push button input) Maximum ON/OFF cycle 2.5 Hz (for push button input) Maximum current consumption 500 mA (5 V DC) 500 mA (5 V DC) Weight 0.3 kg 0.3 kg External connection Pressure clamp terminal Pressure clamp terminal *1: Input a sine wave for AC signals. Yokogawa Digital Input Module NFDV142-P00 Note: AC input signals to the same common should be the same phase. Yokogawa Digital Input Module NFDV142-P00
Item
Specifications
Model
NFDV141
NFDV142
Number of input channels
16
Rated input voltage (*1)
100 to 120 V AC, 50/60 Hz
200 to 240 V AC, 50/60 Hz
Input ON voltage (peak value)
80 V AC (113 V) to 132 V AC (187 V)
160 V AC (226 V) to 264 V AC (373 V)
Input OFF voltage (peak value)
20 V AC (28 V) or less
40 V AC (56 V) or less
Input current (TYP)
4.7 mA (@120 V/60 Hz) / channel
6.2 mA (@240 V/60 Hz) / channel
Input current (MAX)
7 mA / channel
9.3 mA / channel
Withstanding voltage
Between input signal and system: 2 kV AC
Between commons: 1.35 kV AC, common every 8-channel
Functions
Status input
Push button input
Function for detecting ON/OFF status
Function for counting the push button edge
Input response time
160 ms or less (for status input)
Minimum ON detection time
200 ms (for push button input)
Maximum ON/OFF cycle
2.5 Hz (for push button input)
Maximum current consumption
500 mA (5 V DC)
Weight
0.3 kg
External connection
Pressure clamp terminal
Models and Suffix Codes
Digital Input Module
Description Model NFDV142 Digital Input Module (16-channel, 200 V - 240 V AC, Isolated) Suffix Codes -P With function for counting the push button edge 0 General-purpose type 0 Basic type 1 With ISA Standard G3 option Option Code /C4S60 With Pressure Clamp Terminal Block for Digital [Model : NFTC4S-60]
Description
Digital Input Module (16-channel, 200 V - 240 V AC, Isolated)
Suffix Codes
-P
With function for counting the push button edge
0
General-purpose type
Basic type
1
With ISA Standard G3 option
Option Code
/C4S60
With Pressure Clamp Terminal Block for Digital [Model : NFTC4S-60]