Product Information

Yokogawa Analog Input Module NFAI143-H01[Product print page]

Product Name: Yokogawa Analog Input Module NFAI143-H01
Product Type: NFAI143-H01
Exhibitors: Yokogawa
Product Documentation: No Related Documents

Brief

Yokogawa Analog Input Module NFAI143-H01, Yokogawa Analog Input Module NFAI143-H01, 4 to 20mA,16-channel, Isolated. NFAI143-H01 is discontinued, replaced by NFAI143-H51.​


 Detailed description

STARDOM

FCN, FCN-500, FCN-100, FCN-RTU, FCJ

Yokogawa Analog Input Module NFAI143-H01

NFAI143-H01 is discontinued, replaced by NFAI143-H51.

Standard Specifications

Current Input Modules (Isolated)

Input of 4 to 20 mA signals of 16 channels.

Yokogawa Analog Input Module NFAI143-H01

Items

Specifications

Model

NFAI143 (*1) (*4)

Number of input channels

16-channel input, isolated

Input signal

4 to 20 mA

Allowable input current

24 mA

Withstanding voltage

Between input and system: 1500 V AC for 1 minute (*3)

Overcurrent protection

Provided

 

Input resistance

Power ON

250 Ω

Power OFF

500 kΩ or more

Accuracy

±0.1% of full scale

Data refresh cycle

10 ms

Input step response time

100 ms

Transmitter power supply

24.0 to 25.5 V (output current limit:25 mA)

Setting of 2-wire or 4-wire transmitter

For each channel by setting pin

Temperature drift

Max. ±0.01%/°C

 

Maximum current consumption

230 mA (5 V DC)

540 mA (24 V DC)

Weight

0.3 kg

External connection

Pressure clamp terminal, MIL connector cable (*3)

HART Communication(*2)

Available

*1:  When this I/O module is used, 24 V DC needs to be supplied to an analog field power supply terminal of the power supply module.
*2:  For HART function specifications, refer to “HART Communication Functions” (GS 34P02Q53-01E). Yokogawa Analog Input Module NFAI143-H01
*3:  The withstanding voltage for using MIL connector cable depends on the electrical specifications of its cable. If you are using KMS40 cable,            withstanding voltage of between input and system is 500 V AC for 1 minute.
*4:  A Zener barrier is not allowed to be connected with this module. Use an isolation barrier when the module is used in intrinsically safe    application. Yokogawa Analog Input Module NFAI143-H01



Models and Suffix Codes 

Yokogawa Analog Input Module NFAI143-H01

 

 

Description

Model

NFAI143

Analog Input Module (4 to 20mA,16-channel, Isolated)

 

 

 

Suffix Codes

-S

Standard Type

-H

With HART Communication

5

With no explosion protection

E

With explosion protection

0

Basic type

1

With ISA Standard G3 option

 

OptionCodes

/A4S00

With Pressure Clamp Terminal Block for Analog [Model: NFTA4S-00]

/A4S10

With Pressure Clamp Terminal Block for Analog (surge absorber) [Model: NFTA4S-10]

/CCC01

With Connector Cover for MIL Cable [Model: NFCCC01]