Manufacturer: Yokogawa Electric Corporation
32 Wet Contact Outputs with Switch (M4 Terminals)
The Relay Board is used in FIO subsystem of CENTUM VP. Relay input/ output boards are connected in between digital input/output modules (for FIO) and field devices. Relay input boards receive contact signals or voltage input signals of field devices. Yokogawa Relay Board ARM55T-000 Relay output boards receive output signals of the digital output module and amplify by the relay, and then output to field devices. These relay boards support dual- redundant digital input/output modules (for FIO). Yokogawa Relay Board ARM55T-000
STANDARD SPECIFICATIONS
lRelay Boards Detail Specifications
Mechanical Relay Boards (Contact Output)
Models
ARM55D
ARM55W ARM55T (with switch)
ARM55C
Usage
Mechanical RelayDry Contact Output(“a” contact (NO)) (Single / Dual redundant)
Mechanical RelayWet Contact Output(Single / Dual-redundant)AUTO/OFF/ON switch(only for ARM55T)
Mechanical RelayDry Contact Output(“a” contact or “b” contact(NONC))(Single / Dual- redundant) (*6)
Contact Points
32-point
Terminals for Field Device Connection
M4 screws
M3.5 screws (*5)(M4 in power input part)
Modules
ADV551 (DO: 32-point)
+ ATD5A (Terminal block)
ADV561 (DO: 64-point) (*1)
Signal Cables
AKB331 (for 32-point)
AKB337 (for 64-point)
Maximum Load (*2)
250 V AC: 2 A per point
30 V DC: 2 A per point
125 V DC: 0.1 A per point (*3)
250 V AC: 0.6 A per point
30 V DC: 0.6 A per point
30 V DC: 1.5 A per point
Minimum Load
5 V, 10mA
5 V, 10 mA
Power Supply Voltage and Current Consumption of Internal Circuit (require external power supply)
24 V DCMax. 0.65 A
24 V DCMax. 0.85 A
Power Supply for Field Device (require external power supply)
-
Dual-line (supply power per 16-point)
250 V AC: Max. 9.6 A
30 V DC: Max. 9.6 A
125 V DC: Max. 1.6 A
Insulation Resistance
At least 10 MΩ (500 V DC)
Withstanding Voltage
Between field device terminalsand cases: 2 kV
Between 24 V power terminalsand cases: 500 V
Between 24 V power terminalsand field device terminals: 2 kV
Ambient Temperature and Humidity
0 to 50 °C, 10 to 90 %RH
Standards
Safety Standard [CSA] (*3)
EMC standards [CE Marking],[C-Tick Marking]
EMC standards [CE Marking],[C-Tick Marking] (*4)
Size
W: 482.6 mm x H: 132.5 mm (3U)
W: 482.6 mm x H: 177 mm (4U)
Weight
2.2 kg
2.6 kg
*1: Two sets of relay board (ARM55D, ARM55W, ARM55T, or ARM55C) and two sets of signal cable (AKB337) are required for one ADV561.
*2: For inductive loads, connect a spark killer (CR network for AC; diode for DC) in parallel with loads.
*3: For DC, 30 V or less is the requirement for the Safety Standard.
*4: ARM55C is out of scope of the Safety Standards.