 Detailed description

Yokogawa Current/Voltage Input Module AAM11B/ZCT (supports BRAIN)

GENERAL

I/O Modules and I/O Module Nests (for RIO) for CENTUM CS 3000 and CENTUM CS 1000 systems.

STANDARD SPECIFICATIONS

I/O Module Nest

Yokogawa Current/Voltage Input Module AAM11B/ZCT

Power Supply: 5.0 V DC supplied from Model AND50, ANS50, AND20, ANS20 Node Interface Unit or Model PFCS/ PFCD Field Control Station

Installation:   Node Interface Unit, I/O Expansion Rack, or  Model PFCS/PFCD Field Control Station.

External Dimensions: 125mm (W) x 130mm (D) x 248mm (H); 

                       AMN51:  137.5mm (W) x 225mm (D) x 254 (H); 

                      AMN52: 233.3mm (W) x 225mm (D) x 254mm (H)

Weight:  Max. 2.5 kg (AMN52. This weight does not include I/O Modules.)


Installation Restrictions for I/O Module Nest

Yokogawa Current/Voltage Input Module AAM11B/ZCT

Model AMN12 High-speed Nest for Analog I/O Modules (*1)

-Always install in Nest No. 1.

-Do not install any I/O module nests in Nests No. 2 through No. 4.

-When using non-AMN12 I/O Module Nest with AMN12, always install it in Nest No. 5 

Model AMM22T, AMM22TJ (*2)  

-Do not install non-AMM22T, AMM22TJ I/O module below AMM22T, AMM22TJ  because AMM22T, AMM22TJ is a module for thermocouple entry. If there were a heat source below AMM22T, AMM22TJ, a reference junction compensation error occur.

-If there is another module (heat source) below AMM22T, AMM22TJ when using 19” Rack Mountable Type, a thermal shield must be inserted between AMM22T, AMM22TJ and the heat source (See Figures 6 and 7).

Model AMN51 Nest for Communication Cards (*3)

-Only one nest is installable in PFCS/PFCD.  Its position is fixed as Nest No. 2.

AMN52 Nest for PROFIBUS Communication Module

-Only one nest is installable in PFC£.  Its position is fixed as Nests No. 1 and 2. AMN52 cannot be combined with AMN51.

Analog I /O Module

Current/Voltage Input Modules

These modules receive 4-20 mA from 2-wire transmitters and 1-5 V standardized signals. They can also receive signals other than standard 4-20 mA or 1-5 V signals. AAM11B/ZCT can be combined with a transmitter which supports BRAIN communications. Use our BRAIN terminal to specify parameters for a transmitter. Yokogawa Current/Voltage Input Module AAM11B/ZCT

Items

Specifications

Model

AAM11, AAM11B

 

Input signal

 

0 to 10 V DC

0 to 20 mA DC (*1) (*2)

(It is possible to supply power to a transmitter.)

Input resistance

1 M at power-up (100 k at power-down)

250

Allowable input voltage/current

-10 to 30 V DC

40 mA DC or less

 

Supplying power to transmitter

 

-

25.0 to 25.5 V DC (Output current limit: 60 mA DC

or less )

 

Auxiliary voltage output

1 to 5 V DC; Output resistance: 1 or less;

Allowable load resistance: 10 k or more; Signal ground is shared with system

Square root extraction

Specify whether to use square root extraction.

Accuracy

Voltage input: ±4 mV Current input: ±16 µA; Auxiliary voltage output: ±12 mV

 

Effect of ambient temperature change

For 10°C change:

Voltage input: ±4 mV + ± 0.15 % of specified value

Current input: ±32 µA

Auxiliary voltage output: ±24 mV

Data update period

50 ms

Current consumption

300 mA or less (5.0 V DC)

 

Signal isolation

Input signals are isolated between systems

Withstanding voltage: 1500 V AC/min

How installed

Installed in the I/O Module Nest

How connected

Connected to the terminals of the I/O Module Nest with M4 screws

How input signals are specified

Specify input signals and range by software setting.

*1:     This module can be combined with MTL barrier 728. In this case, wiring resistance must be 10 Ω or less and the minimum operating voltage of the 2-wire transmitter must be 12 V DC or less.

*2:    When the power of AAM11B/ZCT is OFF or an abnormal condition occurs, the current input loop is open.
Do not share current signals with other receivers. To share signal, attach Shunt Resistance (250 Ω) to current-output module and share voltage output.