Product Information

Yokogawa mV Input Multiplexer Module AMM22TJ[Product print page]

Product Name: Yokogawa mV Input Multiplexer Module AMM22TJ
Product Type: AMM22TJ
Exhibitors: Yokogawa
Product Documentation: No Related Documents

Brief

Yokogawa mV Input Multiplexer Module AMM22TJ, Yokogawa mV Input Multiplexer Module AMM22TJ for CENTUM CS 3000 and CENTUM CS 1000 systems. Please contact us: tekrachel @ 163.com


 Detailed description

Yokogawa CENTUM CS 3000 and CENTUM CS 1000

Yokogawa mV Input Multiplexer Module AMM22TJ   

The specifications of I/O Modules and I/O Module Nests (for RIO) for CENTUM CS 3000 and CENTUM CS 1000 systems. 

 Yokogawa mV Input Multiplexer Module AMM22TJ


l Multiplexer Module of Yokogawa mV Input Multiplexer Module AMM22TJ


These modules receive up to 16 points from DC voltage, mV, thermocouple and RTS.  Measuring inputs can be specified per point. 


Item

Specifications

Model

AMM12T

AMM22M

AMM22T, AMM22TJ (*2)

AMM32T, AMM32TJ (*3) (*4)

 

Input signal

 

DC voltage

 

mV

Thermocouple JIS, IEC Standard type K, T, J, E, B, R, S

IEC Standard type N

RTS

JIS JPt100 or JIS Pt100 (DIN Pt100)

3-wire type

Input range

-10 to 10 V DC

-100 to 100 mV DC

-100 to 100 mV DC

-200 to 600 °C

Allowable input voltage

-30 to 30 V DC

-0.5 to 4.0 V DC

-0.5 to 4.0 V DC

-

Input resistance

1 M-

-

Signal insulation

Input signals are isolated between systems

Data update period

1 s

Accuracy

±4 mV

±40 µV

±40 µV

±0.15 -

Disconnection detection time

 

-

 

10 s Max.

 

20 s Max.

Disconnection detection current

 

-

 

0.1 µA

Allowable signal source resistance

 

-

 

1 k- Max.

 

1 k- Max.

 

-

Allowable wiring resistance

 

-

 

150 - max. (per wire)


Yokogawa mV Input Multiplexer Module AMM22TJ