Yokogawa Current/Voltage Input Module AAM11B (supports BRAIN)
GENERAL
I/O Modules and I/O Module Nests (for RIO) for CENTUM CS 3000 and CENTUM CS 1000 systems.
STANDARD SPECIFICATIONS
I/O Module Nest
Yokogawa Current/Voltage Input Module AAM11B
Power Supply:
5.0 V DC supplied from Model AND50, ANS50, AND20, ANS20 Node Interface Unit or Model PFCS/
PFCD Field Control Station
Installation: Node Interface Unit, I/O Expansion Rack,
or Model PFCS/PFCD Field Control Station.
External
Dimensions: 125mm (W) x 130mm (D) x 248mm (H);
AMN51: 137.5mm (W) x 225mm (D) x 254 (H);
AMN52: 233.3mm (W) x 225mm (D) x 254mm (H)
Weight: Max. 2.5 kg
(AMN52. This weight does not include
I/O Modules.)
Models
|
Names
|
CS 1000
|
CS 3000
|
Installation Restrictions
(See next page)
|
AFS10S,AFS10D
AFG10S,AFG10D AFG20S,AFG20D
|
PFCS PFCD
|
AMN11
|
Nest for Analog I/O Modules
|
X
|
X
|
X
|
|
AMN12
|
High-Speed Nest for Analog I/O Modules
|
|
X
|
|
(*1)
|
AMN21
|
Nest for Relay I/O Modules
|
X
|
X
|
X
|
|
AMN31
|
Nest for Terminal I/O Modules
|
X
|
X
|
X
|
(*2)
|
AMN32
|
Nest for Connector I/O Modules
|
X
|
X
|
X
|
|
AMN33
|
Nest for Communication Modules
|
X
|
X
|
X
|
|
AMN34
|
Nest for Multipoint Control Analog I/O Modules
|
X
|
X
|
X
|
|
AMN51
|
Nest for Communication Cards
|
X
|
|
X
|
(*3)
|
AMN52
|
Nest for PROFIBUS Communication Module
|
X (*5)
|
|
X (*5)
|
(*4)
|
Installation Restrictions for I/O Module Nest
Yokogawa Current/Voltage Input Module AAM11B
|
Model AMN12 High-speed Nest for Analog I/O Modules (*1)
-Always install in Nest No. 1.
-Do not install any I/O module nests in Nests No. 2 through No. 4.
-When using non-AMN12 I/O Module Nest with AMN12, always install it in Nest No. 5
Model AMM22T, AMM22TJ (*2)
-Do not install non-AMM22T, AMM22TJ I/O module
below AMM22T, AMM22TJ because AMM22T, AMM22TJ is a module for thermocouple entry. If there were a heat source below AMM22T, AMM22TJ, a reference junction compensation
error occur.
-If there is another module (heat source) below AMM22T, AMM22TJ when using 19” Rack Mountable Type,
a thermal shield must be inserted between AMM22T, AMM22TJ
and the heat source (See Figures 6 and 7).
Model AMN51 Nest for Communication Cards (*3)
-Only
one nest is installable in PFCS/PFCD.
Its position is fixed as Nest No. 2.
AMN52 Nest for PROFIBUS Communication Module
-Only one nest is installable in PFC£. Its position is fixed as Nests No. 1 and 2. AMN52 cannot be combined with AMN51.
I/O Modules to be Installed in Control Stations
Yokogawa Current/Voltage Input Module AAM11B
Models
|
I/O Module Names
|
I/O Module(s) to be Installed
|
CENTUM CS 1000
|
CENTUM CS 3000
|
PFCS-S, PFCD-S
|
PFCS-E, PFCD-E
|
PFCS-H, PFCD-H
|
AFS10S,AFS10D AFS20S,AFS20D AFG10S,AFG10D AFG20S,AFG20D
|
-
|
Analog I/O Modules
|
AAM10
|
Current/Voltage Input Module (Simplified Type)
|
X
|
X
|
X
|
X
|
AAM11
|
Current/Voltage Input Module
|
X
|
X
|
X
|
X
|
AAM11B
|
Current/Voltage Input Module (supports BRAIN)
|
X
|
X
|
X
|
X
|
AAM21
|
mV, Thermocouple, and RTD Input Module
|
X
|
X
|
X
|
X
|
AAM21J
|
mV, Thermocouple, and RTD Input Module (supports IEC584-1995, IEC751-1995)
|
X
|
X
|
X
|
X
|
APM11
|
Pulse Input Module
|
X
|
X
|
X
|
X
|
AAM50
|
Current Output Module
|
X
|
X
|
X
|
X
|
AAM51
|
Current/Voltage Output Module
|
X
|
X
|
X
|
X
|
AMC80
|
Multipoint Control Analog I/O Module
|
X
|
X
|
X
|
X
|
-
|
Relay I/O Modules
|
ADM15R
|
Relay Input Module
|
X
|
X
|
X
|
X
|
ADM55R
|
Relay Output Module
|
X
|
X
|
X
|
X
|
-
|
Multiplexer Modules (16 Points, Terminal Type)
|
AMM12T
|
Voltage Input Multiplexer Module
|
X
|
X
|
X
|
X
|
AMM22M
|
mV Input Multiplexer Module
|
X
|
X
|
X
|
X
|
AMM22T
|
Thermocouple Input Multiplexer Module
|
X
|
X
|
X
|
X
|
AMM22TJ
|
Thermocouple Input Multiplexer Module (supports IEC584-1995)
|
X
|
X
|
X
|
X
|
AMM32T
|
RTD Input Multiplexer Module
|
X
|
X
|
X
|
X
|
AMM32TJ
|
RTD Input Multiplexer Module (supports IEC751-1995)
|
X
|
X
|
X
|
X
|
AMM42T
|
2-Wire Transmitter Input Multiplexer Module
|
X
|
X
|
X
|
X
|
AMM52T
|
Output Multiplexer Module
|
X
|
X
|
X
|
X
|
-
|
Multiplexer Modules (Connector Type)
|
AMM12C
|
Voltage Input Multiplexer Module
|
X
|
X
|
X
|
X
|
AMM22C
|
mV Input Multiplexer Module
|
X
|
X
|
X
|
X
|
AMM25C
|
mV Input Multiplexer Module with Thermocouple Interface (15 Points, RJC Input port added)
|
X
|
X
|
X
|
X
|
AMM32C
|
RTD Input Multiplexer Module (16 Points)
|
X
|
X
|
X
|
X
|
AMM32CJ
|
RTD Input Multiplexer Module (16 Points, conforms to IEC751-1995)
|
X
|
X
|
X
|
X
|
-
|
Digital I/O Modules
|
ADM11T
|
Contact Input Module (16 Points, Terminal Type)
|
X
|
X
|
X
|
X
|
ADM12T
|
Contact Input Module (32 Points, Terminal Type)
|
X
|
X
|
X
|
X
|
ADM51T
|
Contact Output Module (16 Points, Terminal Type)
|
X
|
X
|
X
|
X
|
ADM52T
|
Contact Output Module (32 Points, Terminal Type)
|
X
|
X
|
X
|
X
|
ADM11C
|
Contact Input Module (16 Points, Connector Type)
|
X
|
X
|
X
|
X
|
ADM12C
|
Contact Input Module (32 Points, Connector Type)
|
X
|
X
|
X
|
X
|
ADM51C
|
Contact Output Module (16 Points, Connector Type)
|
X
|
X
|
X
|
X
|
ADM52C
|
Contact Output Module (32 Points, Connector Type)
|
X
|
X
|
X
|
X
|
-
|
Communication Modules
|
ACM11
|
RS-232C Communication Module
|
X
|
X
|
X
|
X
|
ACM12
|
RS-422/RS-485 Communication Module
|
X
|
X
|
X
|
X
|
ACM21
|
RS-232C General-purpose Communication Card
|
-
|
X
|
X
|
-
|
ACM22
|
RS-422/RS-485 General-purpose Communication Card
|
-
|
X
|
X
|
-
|
ACM71
|
Ethernet Communication Module (for PFCS/PFCD)
|
-
|
X
|
X
|
-
|
ACF11
|
Fieldbus Communication Module
|
X
|
X
|
X
|
X
|
ACP71
|
PROFIBUS Communication Module
|
-
|
X
|
X
|
-
|
X: Installable
- : Not installed
Analog I /O Module
Current/Voltage Input Modules
These modules receive 4-20 mA from 2-wire transmitters and 1-5 V
standardized signals. They can also
receive signals other than standard 4-20 mA or
1-5 V signals. AAM11B can be combined with a transmitter
which supports BRAIN communications. Use
our BRAIN terminal to specify parameters for a transmitter.
Yokogawa Current/Voltage Input Module AAM11B
Items
|
Specifications
|
Model
|
AAM11, AAM11B
|
Input signal
|
0 to 10 V DC
|
0 to 20 mA DC (*1) (*2)
(It is possible to supply power to a transmitter.)
|
Input resistance
|
1 MΩ at power-up (100 kΩ at power-down)
|
250 Ω
|
Allowable input voltage/current
|
-10 to 30 V DC
|
40 mA DC or less
|
Supplying power to transmitter
|
-
|
25.0 to 25.5 V DC (Output current limit: 60 mA DC
or less )
|
Auxiliary voltage output
|
1 to 5 V DC; Output resistance: 1 Ω or less;
Allowable load resistance: 10 kΩ or more; Signal ground is shared with system
|
Square root extraction
|
Specify whether to use square root extraction.
|
Accuracy
|
Voltage input: ±4 mV; Current input: ±16 µA; Auxiliary voltage output: ±12 mV
|
Effect of ambient temperature change
|
For 10°C change:
Voltage input: ±4 mV + ± 0.15 % of specified value
Current input: ±32 µA
Auxiliary voltage output: ±24 mV
|
Data update period
|
50 ms
|
Current consumption
|
300 mA or less (5.0 V DC)
|
Signal isolation
|
Input signals are isolated between systems
Withstanding voltage: 1500 V AC/min
|
How installed
|
Installed in the I/O Module Nest
|
How connected
|
Connected to the terminals of the I/O Module Nest with M4 screws
|
How input signals are specified
|
Specify input signals and range by software setting.
|
*1: This module can be combined with MTL barrier 728. In this case, wiring resistance must be 10 Ω or less and the minimum operating voltage of the 2-wire transmitter must be 12 V DC or less.
*2: When the power of AAM11B is OFF or an abnormal condition occurs, the current input loop is open.
Do not share current
signals with other receivers. To share signal, attach Shunt Resistance (250 Ω) to current-output module and share voltage output.