Product Information

Yokogawa Relay Output Board MRO[Product print page]

Product Name: Yokogawa Relay Output Board MRO
Product Type: MRO
Exhibitors: Yokogawa
Product Documentation: No Related Documents

Brief

Yokogawa Relay Output Board MRO Yokogawa Relay Output Board MRO for RIO and ST compatible FIO CENTUM VP


 Detailed description

Yokogawa Relay Output Board MRO

Terminal boards are used to connect field I/O signals to I/O modules (for RIO and ST compatible FIO) in I/O module nests of control stations.

Terminal blocks are used to connect I/O signals to I/O modules. Yokogawa Relay Output Board MRO

Relay input boards are connected to digital signals from the field and provide one/two contact output signals per input. When converted into two contact signals, one contact is used as status input and the other is output from a terminal on the top of the board.  Relay output boards output one/two status output signals per relay. Yokogawa Relay Output Board MRO

Relay Output Boards (16points)

Yokogawa Relay Output Board MRO

Model

MRO-114

MRO-124/MRO-134

MRO-144/MRO-154

MRO-164

 

Usage

 

contact output

“NO contact circuit

contact output

“NO contact 2 circuits/

”NO and “NC contacts each one circuit

 

Wet contact output/ Wet output with maintenance switch

 

Wet contact output, Dry contact output

Connecting Module

ADM51C, ADV859, ADV559

Connecting Cable

KS2

 

Contact Rated Load

(TM1) (*2)

 

125 V AC 1 A

24 V DC 1 A

125 V DC 0.1 A

 

125 V AC 1 A

24 V DC 1 A

125 V DC 0.1 A

125 V AC 0.6 A

24 V DC 0.6 A

125 V DC 0.1 A

16 Points total: 5 A or less

125 V AC 0.6 A

24 V DC 0.6 A

125 V DC 0.1 A

16 Points total: 5 A or less

 

Contact Rated Load

(TM2) (*2)

 

250 V AC 1.5 A

24 V DC 1.5 A

125 V DC 0.1 A

 

250 V AC 1.5 A

24 V DC 1.5 A

125 V DC 0.1 A

Contact Minimum Load

(TM1,TM2)

 

5 V, 10 mA

Power Supply Voltage

24 V DC±10 %

Consumption Current (*1)

0.21 A

0.28 A

0.21 A

0.28 A

Insulation Resistance

At Least 20 MΩ 500 V DC

 

 

 

Withstanding Voltage

 

Between Lower terminal “TM1”and Cases:1000 V Between power supply terminal “TM1 and Cases : 500 V

Between Lower terminal “TM1 and Cases:1000 V Between Upper terminal “TM2 and Cases:1500 V Between power supply terminal “TM1 and

Cases : 500 V

 

Between Lower terminal “TM1 and Cases:1000 V Between power supply terminal “TM1 and

Cases : 500 V

Between Lower terminal “TM1 and Cases:1000 V Between Upper terminal “TM2 and Cases: 1500 V Between power supply terminal “TM1 and

Cases : 500 V

Yokogawa Relay Output Board MRO