Discontinued Yokogawa ProSafe-RS Module SDV531-L23, Replaced by SDV531-L53
STANDARD SPECIFICATIONS
Discontinued Yokogawa ProSafe-RS Module SDV531-L23, Replaced by SDV531-L53
Output Module
Discontinued Yokogawa ProSafe-RS Module SDV531-L23, Replaced by SDV531-L53 can be made dual-redundant respectively. They
incorporate field wiring diagnostic functions, so they require no wiring
diagnosis elements.
Item
|
Specifications
|
Model
|
SDV531
|
Number of outputs
|
8-channel, module isolation
|
Output voltage
|
24 V DC
|
Output voltage drop
|
1 V maximum
|
External power supply rating
|
24 V DC, 5 A minimum
|
External power supply
|
24 V DC +20 %/–10 % (*1) Current capacity: 5 A
|
Maximum leak current at output off status
|
1.6 mA
|
Output format
|
Current source
|
Maximum load current
|
0.6 A/output line (4.8 A in total output lines) (*2)
|
Minimum load current
|
35 mA
|
Load resistance range
|
40 to 685 Ω (*3)
|
Output response time
|
30 ms maximum
|
Withstand voltage
|
2 kV AC (between output signal lines and system), 8-point input lines collectively connected (negative lines) (*4)
|
Current consumption
|
280 mA maximum (5 V DC)
140 mA maximum (24 V DC)
|
Weight
|
0.28 kg (For pressure clamp terminal block or MIL cable)
0.34 kg (With dedicated signal cable interface adapter)
|
External connection
|
Pressure clamp terminal
MIL cable
Dedicated signal cable (AKB331, AKB651 (*5))
|
*1: External power supply of SDV531-L23-S style code S1 and S2 is 24 V DC ± 5%.
*2: Do not exceed this value, including
the case of inrush/variation of the load current.
*3: Resistance value of the load for both ON and OFF state, including
the field wiring resistance.
*4: When connecting
SDV531-L23 and SED4D terminal board using AKB331 dedicated signal cable, the withstand voltage is 500
V AC (between
output signal lines and system). If MIL connector cables are used, the withstand voltage depends on their
cable’s electrical
specifications. Discontinued Yokogawa ProSafe-RS Module SDV531-L23, Replaced by SDV531-L53
*5: AKB651 can be used for connection
with SDV531-L23-L only.
MODEL AND SUFFIX CODES
Discontinued Yokogawa ProSafe-RS Module SDV531-L23, Replaced by SDV531-L53
Digital Output Module
|
|
Description
|
Model
|
SDV531
|
Digital output module (8-channel, module isolation)
|
Suffix Codes
|
-L
|
Long distance type
|
-S
|
Standard type
|
5
|
For pressure clamp terminal block or MIL cable with no explosion protection
|
6
|
With signal cable interface adapter and no explosion protection (*1)
|
E
|
For pressure clamp terminal block or MIL cable with explosion protection
|
F
|
With signal cable interface adapter and explosion protection (*1)
|
3
|
With ISA standard G3 and temperature (-20 to 70 °C)
|
Option Codes
|
/B4S00
|
With pressure clamp terminal block for digital output (without surge absorber) [Model: STB4S-00]
|
/B4S10
|
With pressure clamp terminal block for digital output (with surge absorber) [Model: STB4S-10]
|
/B4D00
|
Dual-redundant pressure clamp terminal block for digital output (without surge absorber) (*2) [Model: STB4D-00]
|
/B4D10
|
Dual-redundant pressure clamp terminal block for digital output (with surge absorber) (*2) [Model: STB4D-10]
|
/PRP
|
With prevention pin of false insertion (*3)
|
/CCC01
|
With connector cover for MIL cable (for flat ribbon cable) [Model: SCCC01]
|
/CCC02
|
With connector cover for MIL cable (for discrete wire) [Model: SCCC02]
|
*1: When SDV531-L23-£63 or -£F3 is selected, you cannot choose the option code for a pressure
clamp terminal block and MIL
cable connector.
*2: When this module is used in dual-redundant configuration, order an additional module with the same specification but
without option codes.
*3: When SDV531-L23-£63 or -£F3 is selected, you can choose the option code for prevention pin of false insertion.