Yokogawa Safety Instrumented Systems (SIS)
Yokogawa ProSafe-RS
Discontinued Yokogawa ProSafe-RS Analog Input Module SAI143-H03, Replaced by SAI143-H53
STANDARD SPECIFICATIONS
Current Input Module
This module inputs 4 to 20 mA signals from the field.
The SAI143 can be made dual redundant.
Discontinued Yokogawa ProSafe-RS Analog Input Module SAI143-H03, Replaced by SAI143-H53
Item
|
Specfications
|
Model
|
SAI143 (*1)
|
Number of input channels
|
16-channel, module isolation (*5)
|
Rated input range
|
4 to 20 mA
|
Permissible input range
|
0 to 25 mA
|
Input impedance during P-ON
|
272.5 (20 mA) to 362.5 (4 mA)
|
Input impedance during P-OFF
|
500 k minimum
|
Rated accuracy
|
SAI143-S : ±16 µA (Input range 1 to 23 mA)
SAI143-H : ±16 µA (Input range 0.05 to 23 mA) (*3) (*4)
|
Data update frequency
|
40 ms
|
Temperature drift
|
±16 µA/10 °C
|
Transmitter power supply
|
16.15 V minimum (at 20 mA)
26.4 V maximum (at 0 mA) (Output current limit: 25 mA)
|
2/4-wire setting
|
Individual channel setting
Changed by setting pins
|
Withstand voltage
|
1.5 kV AC between input signal and system (*2)
|
Maximum current consumption
|
5 V system: 320 mA,
24 V system: 550 mA
|
Weight
|
0.34 kg (For pressure clamp terminal block or MIL cable)
0.39 kg (With signal cable interface adapter)
|
External connection
|
Pressure clamp terminal
MIL cable
Dedicated signal cable
|
Support PRM
|
Available (SAI143-H)
|
*1: No Zener barriers can be connected to this module. An isolation barrier should be used when an intrinsic safety instrumented system is used.
*2: 500 V AC when dedicated signal cable is used. Discontinued Yokogawa ProSafe-RS Analog Input Module SAI143-H03, Replaced by SAI143-H63
*3: ±32 µA (input range under 0.05 mA) (Style code S3 or later)
*4: Rated accuracyof style code S3 or later is ±16 µA (Input range 0.05 to 23 mA).
Rated accuracy of style code S2 or earlieris ±16 µA (Input range 1 to 23 mA). Discontinued Yokogawa ProSafe-RS Analog Input Module SAI143-H03, Replaced by SAI143-H53
*5: When SAI143-S£3 or SAI143-H£C is used in the ambienttemperature more than 60°C, number of input channels which a user can use is restricted. Refer to “ProSafe-RS Outline of I/O Modules (GS 32Q06K20-31E)”.
MODEL AND SUFFIX CODES
Discontinued Yokogawa ProSafe-RS Analog Input Module SAI143-H03, Replaced by SAI143-H53
|
|
Description
|
Model
|
SAI143
|
Analog Input Module (4 to 20 mA, 16-channel, module isolation)
|
Suffix Codes
|
-S
|
Standard type
|
-H
|
With HART communication [Release: R1.02.00] (*1)
|
5
|
For pressure clamp terminal block or MIL cable with no explosion protection
|
6
|
With signal cable interface adapter and no explosion protection (*2)
|
E
|
For pressure clamp terminal block or MIL cable with explosion protection
|
F
|
With signal cable interface adapter and explosion protection (*2)
|
3
|
With ISA Standard G3 and temperature (-20 to 70 ºC)
|
C
|
With ISA Standard G3 and high-density installation (-20 to 70 ºC) (*5)
|
Option Codes
|
/A4S00
|
With pressure clamp terminal block for analog
[Model: STA4S-00]
|
/A4S10
|
With pressure clamp terminal block for analog (with surge absorber) [Model: STA4S-10]
|
/A4D00
|
With dual-redundant pressure clamp terminal block for analog (*3) [Model: STA4D-00]
|
/A4D10
|
With dual-redundant pressure clamp terminal block for analog (with surge absorber) (*3) [Part name: STA4D-10]
|
/PRP
|
With prevention pin of false insertion (*4)
|
/CCC01
|
With connector cover for MIL cable (for flat ribbon cable) [Model: SCCC01]
|
*1: For dual-redundant pressure clamp terminal block, please do not use STA4D-£0 S1.
*2: When selecting SAI143-£6£or -£F£, you can not choose the option code of pressure clamp terminal block and MIL cable connector.
*3: When using this module in a dual-redundant configuration, order an additional module with the same specifications but without option codes.
*4: When SAI143-£6£or -£F£is selected, you can choose the option code for prevention pin of false insertion.
A mechanismto prevent wrong type I/O module insertion is supported with signal cable. The signal cable used with this I/O module must have option code /SAI143.
*5: Suffix code for “With ISA StandardG3 and high-density installation” is available in case of SAI143-H£C. This is not available in case of SAI143-S.