Product Information

Yokogawa Safety Control Unit SSC50S-F2541[Product print page]

Product Name: Yokogawa Safety Control Unit SSC50S-F2541
Product Type: SSC50S-F2541
Exhibitors: Yokogawa
Product Documentation: No Related Documents

Brief

Yokogawa Safety Control Unit SSC50S-F2541 Yokogawa Safety Control Unit SSC50S-F2541 Yokogawa ProSafe-RS Yokogawa SIS(Safety Instrumented Systems)


 Detailed description

Yokogawa Safety Control Unit SSC50S-F2541 (for Vnet/IP, 19-inch Rack Mountable)    

 

HARDWARE SPECIFICATIONS

For the criteria for the installation environment, refer to “ProSafe-RS Safety Instrumented System Overview” (GS 32Q01B10-31E).

 

Processor

MIPS R5000 Processor

 

Main Memory Capacity

32 MB

 

Memory Protection at Power Failure

Yokogawa Safety Control Unit SSC50S-F2541

Application program is stored in non-volatile memories.

Processor Module Management Information is stored in the storage memories backed up by a non- rechargeable battery. 

The batterys recommended replacement cycle is three years when it is used under the average ambient temperature of 30 °C or less.

 

Temperature Adaptability

A fan unit is provided for high temperature use where the safety control units (SSC50S-F/SSC50D-S2521-F) ambient temperature exceeds 40 °C.

 

Communications Interface

Vnet/IP interface: Dual-redundant

ESB bus interface: Dual-redundant

 

Communication on Vnet/IP

Communication speed:   100 Mbps, Full duplex

Connection:      UTP cable (CAT5e or higher), RJ45 connector

Interface:           100Base-TX compliance

Max. distance: 100 m (distance between SSC50S/ SSC50D-S2521 and Layer 2 switch)


 Connecting Safety Node Units

 Power Requirements

Specify suffix codes.

Voltage: 100 to 120 V AC, 50 or 60 Hz Voltage: 220 to 240 V AC, 50 or 60 Hz Voltage: 24 V DC

 

Power Consumption

Yokogawa Safety Control Unit SSC50S-F2541

• SSC50S-S/SSC50D-S2521-S

100 to 120 V AC model: 200 VA

200 to 240 V AC model: 230 VA

24 V DC model: 5.5 A

• SSC50S-F/SSC50D-S2521-F

100 to 120 V AC model: 240 VA

200 to 240 V AC model: 290 VA

24 V DC model: 7.0 A

 

Weight

Approximately 7.9 kg (for SSC50S-S) Approximately 13.0 kg (for SSC50S-F) Approximately 8.5 kg (for SSC50D-S2521-S) Approximately 13.0 kg (for SSC50D-S2521-F)

 

Mounting


For each safety control unit, up to nine safety node units can be connected. For installation, ESB bus coupler modules (SEC401) should be mounted on 7-th and 8-th slots.

ESB bus can be extended by Optical ESB bus repeater module.

Yokogawa Safety Control Unit SSC50S-F2541

 Number of I/O Modules Mounted

Up to eight for each safety control unit

Up to 78 for each SCS


MODELS AND SUFFIX CODES

Duplexed Safety Control Unit (for Vnet/IP, 19-inch Rack Mountable)

Yokogawa Safety Control Unit SSC50S-F2541

   

[Style: S1]

   

Description

Model

  SSC50S

Safety Control Unit (for Vnet/IP, 19-inch Rack Mountable)

Suffix Codes

-S

Standard Type (with ISA Standard G3)

-F

Wide range temperature (-20 to 70 °C) type (with Fan unit and ISA Standard G3)

2

Dual-redundant power supply

5

With no explosion protection

E

With explosion protection

 

1

100-120V AC power supply

 

2

220-240V AC power supply

 

4

24 V DC power supply

 

 1

CFS1100 Safety Control Function License

Option Code

/ATDOC

Explosion protection manual

/ERFI

Enhanced RFI