Yokogawa Digital Input Module ADV157-S00

Standard specifications:  

Yokogawa Digital Input Module ADV157-S00

Item

Specifications

Model

ADV151-P/ADV151-E (*1)

ADV157

ADV161

Number of input channels

32

32

64

Rated input voltage (*2)

24 V DC (sink/source)

24 V DC (sink/source)

24 V DC (sink/source)

Input ON voltage

18 to 26.4 V DC

18 to 26.4 V DC

20 to 26.4 V DC

Input OFF voltage

5.0 V DC or less

5.0 V DC or less

5.0 V DC or less

Input current (at rated input voltage)

4.1 mA±20 % / channel

4.1 mA±20 % / channel

2.5 mA±20 % / channel

Maximum allowable input voltage

30.0 V DC

30.0 V DC

30.0 V DC

Withstanding voltage

Between input signal and system: 2 kV AC, For 1 minute Between commons: 500 V AC, For 1 minute, common every 16-channel (*3)

Functions

Status input

 

Pushbutton input

 

Function for detectingON/OFF status

Function for detecting pushbutton edges

 

Function for detecting

ON/OFF status

—Yokogawa Digital Input Module ADV157-S00

 

Function for detecting ON/OFF status

Function for counting the pushbutton edges

Input response time

8 ms or less (for status input)

Minimum ON detection time

20 ms (for pushbutton input)

Maximum ON/OFF cycle

25 Hz (for pushbutton input) 

Maximum current consumption

500 mA (5 V DC)

350 mA (5 V DC)

550 mA (5 V DC)

Weight

0.3 kg

0.4 kg

0.3 kg

External connection

Pressure clamp terminal,Dedicated cable (AKB331),MIL connector cable

Pressure clamp terminal. Yokogawa Digital Input Module ADV157-S00

Dedicated cable (AKB337),MIL connector cable

 

Models and Suffix Codes:    

Yokogawa Digital Input Module ADV157-S00  

 

 

Description

Model

ADV157

Digital Input Module (32-channel, 24 V DC, Pressure Clamp Terminal support only, Isolated)

Suffix Codes

-S

Standard type

       5

With no explosion protection

       E

With explosion protection

            0

Basic type

            1

With ISA Standard G3 option