Product Information

Yokogawa AC Digital Input Module ADV141 [Product print page]

Product Name: Yokogawa AC Digital Input Module ADV141
Product Type: ADV141
Exhibitors: Yokogawa
Product Documentation: No Related Documents

Brief

Yokogawa AC Digital Input Module ADV141, Yokogawa AC Digital Input Module ADV141, Yokogawa CENTUM VP, Yokogawa DCS


 Detailed description

Yokogawa AC Digital Input Module ADV141   

 

AC Digital Input Modules

The AC Digital Input Modules receive 16-channel 100 V AC or 220 V AC ON/OFF signals.

They can be used in dual redundant configuration.


Standard specifications:

Yokogawa AC Digital Input Module ADV141    

Item

Specifications

Model

ADV141

ADV142

Number of input channels

16

16

Rated input voltage (*1)

100 to 120 V AC, 50/60 Hz

200 to 240 V AC, 50/60 Hz

Input ON voltage (peak value)

80 V AC (113 V) to 132 V AC (187 V)

160 V AC (226 V) to 264 V AC (373 V)

Input OFF voltage (peak value)

20 V AC (28 V) or less

40 V AC (56 V) or less

Input current (TYP)

4.7 mA (@120 V/60 Hz) / channel

6.2 mA (@240 V/60 Hz) / channel

Input current (MAX)

7 mA / channel

9.3 mA / channel

Withstanding voltage

Between input signal and system: 2 kV AC, For 1 minute

Between commons: 1.35 kV AC, For 1 minute, common minus (–) side every 8-channel

Functions

Status input

Pushbutton input

 Function for detecting ON/OFF status

Function for counting the pushbutton edges. Yokogawa AC Digital Input Module ADV141

Input response time

160 ms or less (for status input)

Minimum ON detection time

200 ms (for pushbutton input)

Maximum ON/OFF cycle

2.5 Hz (for pushbutton input). Yokogawa AC Digital Input Module ADV141

Maximum current consumption

500 mA (5 V DC)

500 mA (5 V DC)

Weight

0.3 kg

0.3 kg

External connection

Pressure clamp terminal,

Dedicated cable (AKB332)

Pressure clamp terminal,

Dedicated cable (AKB333)

 

Models and Suffix Codes   

Yokogawa AC Digital Input Module ADV141

 

 

Description

Model

ADV141

Digital Input Module (16-channel 100 - 120 V AC Isolated)

Suffix Codes

-P

With pushbutton input

      5

Without status display; with no explosion protection

      E

Without status display; with explosion protection

            0

Basic type

            3

With ISA Standard G3 option and temperature (-20 to 70 °C) option

Option Code

/C4S50

With Pressure Clamp Terminal Block for Digital [Model : ATC4S-50]