Standard specifications:
Items
Specifications
Model
AAT141
AAR181
Number of input channels
16, isolated (*7)
12, isolated
Input signal
TC: JIS C1602:1995, IEC584:1995 Type J, K, E, B(*1), R, S, T, N mV: -100 to 150 mV, -20 to 80 mV
RTD: JIS C1604:1997, IEC751:1995 Pt100 (3-wire type)(*6)
Switching input signals
TC/mV can be set individually for CH1 to CH16.
CH1 to CH12 are RTD inputs.
Allowable input voltage
±5 V
Withstanding voltage
Between input and system: 1500 V AC, For 1 minute
Input resistance
Power ON
2 MΩ or more. Yokogawa RTD Input Module AAR181-S50
Power OFF
2 MΩ or more
Accuracy
TC: ±30 μV. MV: ±80 μV for span (-100 to 150 mV), ±30 μV for span (-20 to 80 mV)
RTD: ±120 mΩ
Allowable total resistance of signal source plus wiring
1000 Ω or less
40 Ω or less (wiring resistance per wire) (*2)
Effect of allowable signal source resistance (1000 Ω)
±20 μV(*3)
—
Reference junction compensation accuracy
Within ±1 °C (*4) (*5)
Measurement current
RTD: 1 mA
Temperature drift
±80 μV/10 C degree (-100 to 150 mV input) ±30 μV/10 C degree (TC/-20 to 80 mV input)
±120 mΩ/10 C degree (RTD input)
Data update period
1 s
Burn-out
All channels can be set together. Setting: Not available/available (UP/DOWN) detection time: 60 s
Maximum current consumption
450 mA (5 V DC)
Weight
0.2 kg
External connection
Pressure clamp terminal
*1: Type B dose not carry out temperature compensation and can not measure under 44 °C
*2: Wiring resistance for the signal cables of IN A and IN C must be identical. Yokogawa RTD Input Module AAR181-S50
*3: In dual redundant configuration, this effect is ±40 μV.
*4: This accuracy changes due to the installation condition.
If measured temperature is lower than 0 °C, multiply the above value by the following coefficient (K):
Models and Suffix Codes:
Description
RTD Input Module (12-channel, Isolated)
Suffix Codes
-S
Standard type
5
With no explosion protection
E
With explosion protection
0
Basic type
3
With ISA Standard G3 option and temperature (-20 to 70 °C) option
Option Codes
/R8S00
With Pressure Clamp Terminal Block for RTD [Model: ATR8S-00]
/R8S10
With Pressure Clamp Terminal Block for RTD (surge absorber) [Model: ATR8S-10]
/R8D00
With Dual Pressure Clamp Terminal Block for RTD [Model: ATR8D-00]
/R8D10
With Dual Pressure Clamp Terminal Block for RTD (surge absorber) [Model: ATR8D-10]
/CCC01
With Connector Cover for MIL Cable [Model: ACCC01]
Contact Number: +86 13724889019 Email: tekrachel2024@163.com Web: www.tek-international.com WeChat: tekrachel tekrachel@163.com
Add.: Room 2401 Building D Greenland Central Plaza, Science City, Huangpu District, Guangzhou 510663, Guangdong Province, China.