YOKOGAWA CENTUM VP, VNET/IP
Yokogawa Field Control Unit FCU AFV30S-S41251
Hardware Specifications for Yokogawa Field Control Unit FCU AFV30S-S41251
For the installation specifications and the environmental conditions common to the systems, refer to “Vnet/IP System Overview (Vnet/IP Edition)”.
Processor
VR5432 (133 MHz)
Main Memory Capacity
32 Mbyte
Memory Protection During Power Failure to Yokogawa Field Control Unit FCU AFV30S-S41251
Battery
Battery Back-up for Main Memory: Max. 72 hours
Battery Recharge Time: Min. 48 hours
FCU Status Contact Output
2 terminals (NC, C)
Contact Points open during FCU failure
Contact Rating: 30 V DC, max. 0.3 A
Communication Interface
Vnet/IP Interface: Dual-redundant
Power Supply
Voltage: 100-120 V AC, Frequency: 50/60 Hz
Voltage: 220-240 V AC, Frequency: 50/60 Hz
Voltage: 24 V DC
Specify with Suffix Codes.
Power Consumption
100-120 V AC: 200 VA
220-240 V AC: 230 VA
24 V DC: 5.5 A
Weight for Yokogawa Field Control Unit FCU AFV30S-S41251
Approx. 7 kg (AFV10S)
Approx. 8 kg (AFV10D)
Mounting for Yokogawa Field Control Unit FCU AFV30S-S41251
19-inch Rack Mounting:
Rack mount (8 x M5 screws)
Insulation bush (accessory)
Connection
Power Supply: M4 screw terminal connection Grounding: M4 screw terminal connection Contact Output: M4 screw terminal connection Network: Connect UTP cable (CAT5e or better) to Layer 2 switch.
Standard Accessoriesfor Yokogawa Field Control Unit FCU AFV30S-S41251
The FCU is delivered with the following standard accessories.
Parts Names
|
Parts Numbers
|
Description
|
Quantity
|
Remarks
|
Insulating bush
|
S9049PM
|
–
|
8
|
Accessory
|
Models and Suffix Codes for Yokogawa Field Control Unit FCU AFV30S-S41251
Field Control Unit
|
|
Description
|
Model
|
AFV30S
|
Field Control Unit (for Vnet/IP and FIO, 19-inch Rack Mountable)
|
Suffix
Codes
|
-S
|
Standard type
|
3
|
Dual-redundant Vnet/IP, single power supply
|
4
|
Dual-redundant Vnet/IP, dual-redundant power supply
|
1
|
Always 1
|
1
|
100 - 120 V AC power supply (*1)
|
2
|
220 - 240 V AC power supply (*1)
|
4
|
24 V DC power supply (*1)
|
5
|
Basic type with no explosion protection
|
6
|
With ISA Standard G3 option and no explosion protection
|
E
|
Basic type with explosion protection
|
F
|
With ISA Standard G3 option and explosion protection
|
1
|
LFS1700 Control function for field control station
(for AFV30£/AFV40£, Vnet/IP and FIO) <for CP461>
|
Option
Codes
|
/HKU
|
With HKU interface (*2)
|
/ATDOC
|
Explosion Protection Manual (*3)
|
Note:
*1: To meet the safety standards and EMC standards, the unit must be installed in a keyed metallic cabinet.
*2: When used in combination with ACUKT, specify this option code “/HKU.”
*3: Select the option code “/ATDOC” to follow the ATEX Directive for use in potentially explosive atmospheres.