 Detailed description

YOKOGAWA CENTUM VP, VNET/IP

Yokogawa Field Control Unit (FCU) AFV30S-S41151

Hardware Specifications for Yokogawa Field Control Unit (FCU) AFV30S-S41151


For the installation specifications and the environmental conditions common to the systems, refer to “Vnet/IP System Overview (Vnet/IP Edition)”.

FCU Status Contact Output

2 terminals (NC, C)

Contact Points open during FCU failure

Contact Rating: 30 V DC, max. 0.3 A

 

Communication Interface

Vnet/IP Interface: Dual-redundant

 

No. of Node Units Connectable

Max. 14/FCU

The total number of ESB Bus Node Units and ER Bus Node Units that can be connected to FCU are 14 or less. (ESB Bus Node Units: 9 or less)

LFS1500 allows up to 3 nodes, and can be expanded to 14 if LFS1550 Application capacity Expansion Package (for AFV10 ) is added.

To connect a node unit to the FCU, a Node Unit Expansion License (Option code: /NDEL) is required for the node unit.

 

Module configuration for Yokogawa Field Control Unit (FCU) AFV30S-S41151

Power Supply Module (PW481 or PW482 or PW484):

Two modules in case of a dual-redundant configuration.

Processor Module (CP451): Two modules in case of a dual-redundant configuration.

I/O Modules(*1): Max. 8

*1: Non-standard components.


ESB Bus Node Units Connection

When connecting an ESB Bus Node Unit to FCU, install ESB Bus Coupler Module (EC401) on FCU. EC401 must be installed in slot 7 and slot 8. For the dual-redundant configuration of the processor modules, EC401 must be installed in both slot 7 and slot 8.

In case ESB Bus has a single configuration, EC401 must be installed in slot 7 and keep slot 8 empty.

 

ER Bus Node Units Connection for Yokogawa Field Control Unit (FCU) AFV30S-S41151

When connecting an ER Bus Node Unit to FCU, install ER Bus Interface Master Module (EB401) on FCU.

To make single configuration, EB401 must be installed in an odd-number slot, and keep empty the right side of the installed EB401.

See “ER Bus Interface Master Module (for FIO)” (GS 33K50F40-50E) for further information.

 

Power Supply

Voltage: 100-120 V AC, Frequency: 50/60 Hz

Voltage: 220-240 V AC, Frequency: 50/60 Hz

Voltage: 24 V DC

Specify with Suffix Codes.

 

Power Consumption

100-120 V AC: 200 VA

220-240 V AC: 230 VA

24 V DC: 5.5 A

 

Weight for Yokogawa Field Control Unit (FCU) AFV30S-S41151

Approx. 7 kg (AFV10S)

Approx. 8 kg (AFV10D)

 

Mounting for Yokogawa Field Control Unit (FCU) AFV30S-S41151

19-inch Rack Mounting:

Rack mount (8 x M5 screws)

Insulation bush (accessory)

 

Connection

Power Supply: M4 screw terminal connection Grounding: M4 screw terminal connection Contact Output: M4 screw terminal connection Network: Connect UTP cable (CAT5e or better) to Layer 2 switch.


Standard Accessories for Yokogawa Field Control Unit (FCU) AFV30S-S41151

The FCU is delivered with the following standard accessories.

Parts Names

Parts Numbers

Description

Quantity

Remarks

Insulating bush

S9049PM

8

Accessory


Models and Suffix Codes for Yokogawa Field Control Unit (FCU) AFV30S-S41151

Field Control Unit

 

 

Description

Model

AFV30S

Field Control Unit (for Vnet/IP and FIO, 19-inch Rack Mountable)

 

 

 

 

 

 

Suffix

Codes

-S

Standard type

3

Dual-redundant Vnet/IP, single power supply

4

Dual-redundant Vnet/IP, dual-redundant power supply

1

Always 1

1

100 - 120 V AC power supply (*1)

2

220 - 240 V AC power supply (*1)

4

24 V DC power supply (*1)

5

Basic type with no explosion protection

6

With ISA Standard G3 option and no explosion protection

E

Basic type with explosion protection

F

With ISA Standard G3 option and explosion protection

 

1

LFS1700 Control function for field control station

(for AFV30£/AFV40£, Vnet/IP and FIO) <for CP461>

Option

Codes

/HKU

With HKU interface (*2)

/ATDOC

Explosion Protection Manual (*3)

Note: 
*1: To meet the safety standards and EMC standards, the unit must be installed in a keyed metallic cabinet.
*2: When used in combination with ACUKT, specify this option code “/HKU.”
*3: Select the option code “/ATDOC” to follow the ATEX Directive for use in potentially explosive atmospheres.