YOKOGAWA CENTUM VP, VNET/IP
Yokogawa FCU AFV30S-S31151
Hardware Specifications for Yokogawa FCU AFV30S-S31151
Processor
VR5432 (133 MHz)
Main Memory Capacity
32 Mbyte
Module configuration
Power Supply Module (PW481 or PW482 or PW484):
Two modules in case of a dual-redundant configuration.
Processor Module (CP451): Two modules in case of a dual-redundant configuration.
I/O Modules(*1): Max. 8
*1: Non-standard components.
ESB Bus Node Units Connection
When connecting an ESB Bus Node Unit to FCU, install ESB Bus Coupler Module (EC401) on FCU. EC401 must be installed in slot 7 and slot 8. For the dual-redundant configuration of the processor modules, EC401 must be installed in both slot 7 and slot 8.
In case ESB Bus has a single configuration, EC401 must be installed in slot 7 and keep slot 8 empty.
ER Bus Node Units Connection
When connecting an ER Bus Node Unit to FCU, install ER Bus Interface Master Module (EB401) on FCU.
To make single configuration, EB401 must be installed in an odd-number slot, and keep empty the right side of the installed EB401.
Power Consumption
100-120 V AC: 200 VA
220-240 V AC: 230 VA
24 V DC: 5.5 A
Weight for Yokogawa FCU AFV30S-S31151
Approx. 7 kg (AFV10S)
Approx. 8 kg (AFV10D)
Mounting for Yokogawa FCU AFV30S-S31151
19-inch Rack Mounting:
Rack mount (8 x M5 screws)
Insulation bush (accessory)
Connection for Yokogawa FCU AFV30S-S31151
Power Supply: M4 screw terminal connection Grounding: M4 screw terminal connection Contact Output: M4 screw terminal connection Network: Connect UTP cable (CAT5e or better) to Layer 2 switch.
Standard Accessories for Yokogawa FCU AFV30S-S31151
The FCU is delivered with the following standard accessories.
Parts Names
|
Parts Numbers
|
Description
|
Quantity
|
Remarks
|
Insulating bush
|
S9049PM
|
–
|
8
|
Accessory
|
Models and Suffix Codes for Yokogawa FCU AFV30S-S31151
Field Control Unit
|
|
Description
|
Model
|
AFV30S
|
Field Control Unit (for Vnet/IP and FIO, 19-inch Rack Mountable)
|
Suffix
Codes
|
-S
|
Standard type
|
3
|
Dual-redundant Vnet/IP, single power supply
|
4
|
Dual-redundant Vnet/IP, dual-redundant power supply
|
1
|
Always 1
|
1
|
100 - 120 V AC power supply (*1)
|
2
|
220 - 240 V AC power supply (*1)
|
4
|
24 V DC power supply (*1)
|
5
|
Basic type with no explosion protection
|
6
|
With ISA Standard G3 option and no explosion protection
|
E
|
Basic type with explosion protection
|
F
|
With ISA Standard G3 option and explosion protection
|
1
|
LFS1700 Control function for field control station
(for AFV30£/AFV40£, Vnet/IP and FIO) <for CP461>
|
Option
Codes
|
/HKU
|
With HKU interface (*2)
|
/ATDOC
|
Explosion Protection Manual (*3)
|
Note:
*1: To meet the safety standards and EMC standards, the unit must be installed in a keyed metallic cabinet.
*2: When used in combination with ACUKT, specify this option code “/HKU.”
*3: Select the option code “/ATDOC” to follow the ATEX Directive for use in potentially explosive atmospheres.