Product Information

Yokogawa Field Control Unit AFV10S-S41251[Product print page]

Product Name: Yokogawa Field Control Unit AFV10S-S41251
Product Type: AFV10S-S41251
Exhibitors: Yokogawa
Product Documentation: No Related Documents

Brief

Yokogawa Field Control Unit AFV10S-S41251, for Vnet/IP and FIO, 19-inch Rack Mountable Type, Yokogawa Field Control Unit AFV10S-S41251. Please contact us: tekrachel @ 163.com


 Detailed description

Manufacturer: Yokogawa Electric Corporation

Yokogawa Field Control Unit AFV10S-S41251

for Vnet/IP and FIO, with 19 inch rack mountable type

Hardware Specifications

Yokogawa Field Control Unit AFV10S-S41251, for Vnet/IP and FIO, with 19 inch rack mountable type  

For the installation specifications and the environmental conditions common to the systems, refer to “Vnet/IP System Overview (Vnet/IP Edition)” (GS 33K01A10- 50E).

 

Processor

VR5432 (133 MHz)

 

Main Memory Capacity

32 Mbyte

 

Memory Protection During Power Failure

Battery

Battery Back-up for Main Memory: Max. 72 hours

Battery Recharge Time: Min. 48 hours

 

FCU Status Contact Output

2 terminals (NC, C)

Contact Points open during FCU failure

Contact Rating: 30 V DC, max. 0.3 A

 

Communication Interface

Vnet/IP Interface: Dual-redundant

 

For more details, refer to “Integrated Production Control System CENTUM VP System Overview (Vnet/IP Edition)” (GS 33K01A10-50E).

 

No. of Node Units Connectable

Max. 14/FCU

The total number of ESB Bus Node Units and ER Bus Node Units that can be connected to FCU are 14 or less. (ESB Bus Node Units: 9 or less)

LFS1500 allows up to 3 nodes, and can be expanded to 14 if LFS1550 Application capacity Expansion Package (for AFV10 ) is added.

To connect a node unit to the FCU, a Node Unit Expansion License (Option code: /NDEL) is required for the node unit.

 

Module configuration

Power Supply Module (PW481 or PW482 or PW484):

Two modules in case of a dual-redundant configuration.

Processor Module (CP451): Two modules in case of a dual-redundant configuration.

I/O Modules(*1): Max. 8

*1: Non-standard components.

 

ESB Bus Node Units Connection

Yokogawa Field Control Unit AFV10S-S41251

When connecting an ESB Bus Node Unit to FCU, install ESB Bus Coupler Module (EC401) on FCU. EC401 must be installed in slot 7 and slot 8. For the dual-redundant configuration of the processor modules, EC401 must be installed in both slot 7 and slot 8.

In case ESB Bus has a single configuration, EC401 must be installed in slot 7 and keep slot 8 empty.

 

ER Bus Node Units Connection

When connecting an ER Bus Node Unit to FCU, install ER Bus Interface Master Module (EB401) on FCU.

To make single configuration, EB401 must be installed in an odd-number slot, and keep empty the right side of the installed EB401.

See “ER Bus Interface Master Module (for FIO)” (GS 33K50F40-50E) for further information.

 

Power Supply

Voltage: 100-120 V AC, Frequency: 50/60 Hz

Voltage: 220-240 V AC, Frequency: 50/60 Hz

Voltage: 24 V DC

Specify with Suffix Codes.

 

Power Consumption

100-120 V AC: 200 VA

220-240 V AC: 230 VA

24 V DC: 5.5 A

 

Weight

Approx. 7 kg (AFV10S)

Approx. 8 kg (AFV10D)

 

Mounting

19-inch Rack Mounting:

Rack mount (8 x M5 screws)

Insulation bush (accessory)

 

Connection

Power Supply: M4 screw terminal connection Grounding: M4 screw terminal connection Contact Output: M4 screw terminal connection Network: Connect UTP cable (CAT5e or better) to Layer 2 switch.

 

Regulatory Compliance

Yokogawa Field Control Unit AFV10S-S41251

For the detailed information of following standards, see “System Overview (Vnet/IP Edition)” (GS 33K01A10-50E).

Safety Standards

[CSA] (for 100-120 V AC power supply)

[CE Marking] (for 220-240 V AC power supply)

EMC Conformity Standards

[CE Marking] (for 220-240 V AC and 24 V DC power supply)

[C-Tick Marking] (for 220-240 V AC and 24 V DC power supply)

[KC Marking] (for 220-240 V AC and 24 V DC power supply)

Standards for Hazardous Location Equipment

[FM Non-Incendive] (for 100-120 V AC, 220-240 V AC and 24 V DC power supply)

[Type n] (for 24 V DC power supply)

Yokogawa Field Control Unit AFV10S-S41251


Insulating Partition Kit

 

 

Description

Part No.

T9083ND

Insulating Partition Kit


Configuration of Insulating Partition Kit

 

 

Description

 

Part No.

T9083NE

Insulating Partition

T9083NG

Insulating Partition for V net

Y9306LB

2 screws for T9083NG