Yokogawa Duplexed Safety Control Unit SSC60D-F2521
HARDWARE SPECIFICATIONS
For the criteria for the installation environment,
refer to “ProSafe-RS Safety Instrumented System Overview” (GS 32Q01B10-31E).
Processor
MIPS R5000 Processor
Main Memory Capacity
128 MB
Memory Protection at Power Failure
Application program is stored in non-volatile memories.
Processor Module Management Information is stored in the storage memories backed up by a
non- rechargeable battery.
The battery’s recommended replacement cycle is three years when it is used
under the average ambient temperature of 30 °C or less.
Temperature Adaptability
A fan
unit is provided for high temperature use where the safety control units
(SSC60S-F/SSC60D-F) ambient temperature exceeds 40 °C.
Communications Interface
Vnet/IP interface:
Dual-redundant
ESB bus interface: Dual-redundant
Communication on Vnet/IP
Yokogawa Duplexed Safety Control Unit SSC60D-F2521
Communication speed: 100
Mbps, Full duplex
Connection: UTP cable (CAT5e
or higher), RJ45 connector
Interface: 100 Base-TX compliance
Max. distance: 100 m (distance between SSC60S/ SSC60D and Layer 2 switch)
Connecting Safety Node Units
Up to 13 safety node units can be connected to a
safety control unit using SEC402 ESB bus coupler module and adding CFS1350 Node
Expansion Package.
Up to 9 safety node units can be connected to a
safety control unit using SEC401 ESB bus coupler module.
For installation, ESB
bus coupler modules (SEC402/ SEC401) should be mounted on 7-th and 8-th slots.
ESB bus can be
extended by Optical ESB bus repeater modules.
Number of I/O Modules Mounted
Up to eight for each safety control unit
Up to 110
for each SCS (using SEC402 ESB bus coupler module and CFS1350 Node Expansion
Package)
Up to 78 for each SCS (using SEC401 ESB bus
coupler module)
Power Requirements
Specify suffix codes.
Voltage: 100 to
120 V AC, 50 or 60 Hz Voltage: 220 to 240 V AC, 50 or 60 Hz Voltage: 24 V DC
Power Consumption
Yokogawa Duplexed Safety Control Unit SSC60D-F2521
• SSC60S-S/SSC60D-S
100 to 120 V AC
model: 200 VA
200 to 240 V AC
model: 230 VA
24 V DC model: 5.5 A
• SSC60S-F/SSC60D-F
100 to 120 V AC
model: 240 VA
200 to 240 V AC
model: 290 VA
24 V DC model: 7.0 A
Weight
Approximately 7.9 kg (for SSC60S-S)
Approximately 13.0 kg (for SSC60S-F)
Approximately 8.5 kg (for SSC60D-S)
Approximately 13.0 kg (for SSC60D-F)
Mounting
Rack
mounting: SSC60S-S/SSC60D-S rack mounted with eight M5 screws
SSC60S-F/SSC60D-F rack mounted with twelve M5
screws
Insulating Bushing: Supplied as accessories
Connections
Power Supply: Connected with M4 screws.
Grounding: Connected with M4 screws.
MODEL AND SUFFIX CODES
Duplexed Safety Control Unit
Yokogawa Duplexed Safety Control Unit SSC60D-F2521
|
|
Description
|
Model
|
SSC60D
|
Duplexed Safety Control Unit (for Vnet/IP, Rack Mountable Type)
|
Suffix
Codes
|
-S
|
Standard Type (-20 to 40 °C) (with ISA Standard G3 )
|
-F
|
Wide range temperature (-20 to 70 °C) type (with Fan unit and ISA Standard G3)
|
2
|
Dual-redundant power supply
|
5
|
With no explosion protection
|
E
|
With explosion protection
|
1
|
100-120 V AC power supply
|
2
|
220-240 V AC power supply
|
4
|
24 V DC power supply
|
1
|
CFS1300 Safety Control Function License
|
Option
Code
|
/ATDOC
|
Explosion Protection Manual
|
Note: Install the 19-inch rack mountable type devices in a keyed metallic
cabinet to conform to the safety standards, the EMC
conformity standards and the explosion
protection standards.
For details, refer to ProSafe-RS
Installation Guidance (TI 32S01J10-01E).
Note: Select the option code “/ATDOC” to follow the ATEX Directive for use in potentially explosive atmospheres.
STANDARD ACCESSORIES
Yokogawa Duplexed Safety Control Unit SSC60D-F2521
Accessory
|
Part number
|
Description
|
Quantity
|
Remark
|
Insulating bushing
|
S9049PM
|
SSC60S-S/ SSC60D-S
|
8
|
Accessories
|
SSC60S-F/ SSC60D-F
|
12
|
|
|
The safety control
unit is supplied with the following accessories.