Product Information

Yokogawa Analog I/O Module AAI835-S50/K4A00[Product print page]

Product Name: Yokogawa Analog I/O Module AAI835-S50/K4A00
Product Type: AAI835-S50/K4A00
Exhibitors: Yokogawa
Product Documentation: No Related Documents

Brief

Yokogawa Analog I/O Module AAI835-S50/K4A00 AAI141 Analog Input Module (4 to 20 mA, 16-channel, Isolated) Yokogawa Analog I/O Module AAI835-S50/K4A00


 Detailed description

Yokogawa Analog I/O Module AAI835-S50/K4A00


GENERAL

Yokogawa Analog I/O Modules AAI835-S50/K4A00
This document describes about hardware specifications of Yokogawa Analog I/O Modules AAI835-S50/K4A00 to be installed in the ESB bus node units (ANB10S and ANB10D), Optical ESB bus node units (ANB11S and ANB11D), and field control units (for FIO) (AFV30S, AFV30D, AFV40S, AFV40D, AFV10S, AFV10D). Yokogawa Analog I/O Module AAI835-S50/K4A00
TheseYokogawa Analog I/O Modules AAI835-S50/K4A00 function as signal converters; by inputting field analog signals into these modules,
it converts them to internal data for field control stations (FCS), or the FCS’s internal data to analog signals for outputs.


HART Communication Functional Specifications

Yokogawa Analog I/O Module AAI835-S50/K4A00

The analog I/O modules (with HART communication function) are equipped with HART modems and eable HART
communication (*1) by directly connecting the HART devices to he modules. Yokogawa Analog I/O Module AAI835-S50/K4A00
No. of HART devices: Max. 16 devices/module
HART variables:  Max. 32 points/module
HART variables can be treated as ordinary process input data via %Z terminal connection. It is just for input.
HART multidrop connection (*2):  Max. 5 devices/channel
HART variables data refresh cycle time :
1 second/device (When maximum of 16 devices are connected, it is 17 seconds per ESB bus connection.)
Yokogawa Analog I/O Module AAI835-S50/K4A00
*1: HART communication refers to HART variable communicaiton, on-demand communication, and hand held terminal (HHT)
communication.
*2: It is possible to connect only input devices. This connection does not support analog data value nor burst function