Product Information

Yokogawa ER Bus Node Unit ANR10D-423[Product print page]

Product Name: Yokogawa ER Bus Node Unit ANR10D-423
Product Type: ANR10D-423
Exhibitors: Yokogawa
Product Documentation: No Related Documents

Brief

Yokogawa ER Bus Node Unit ANR10D-423 Yokogawa ER Bus Node Unit ANR10D-423 for Dual-Redundant ER Bus


 Detailed description

Manufacturer: Yokogawa Electric Corporation

Yokogawa control system: CENTUM VP

Yokogawa ER Bus Node Unit ANR10D-423

The ER Bus Node Unit has an interface function that communicates the analog I/O signals and contact I/O signals of a field with a Field Control Unit (FCU), as well as a function that supplies power to the I/O Modules.  

 

ANB10S ANB10D image.jpg

Yokogawa ER Bus Node Unit ANR10D-423

Hardware specifications

No. of Node Units Connectable

Vnet/IP

 

Field Control Unit

Database

ESB Bus Node Units (ANB10 ) Connected per FCU

ER Bus Node Units (ANR10 )Connected per FCU

Total Number of ESB Bus Node Units ( ANB10 ) and ER Bus Node Units (ANR10 )Connected per FCU

AFV10

Control Function for Field Control Station (LFS1500)

Max. 3

Max. 3

Max. 3

Control Function for Field Control Station (LFS1500) plus Application Capacity Expansion Package (LFS1550)

Max. 9

Max. 14

Max. 14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vnet

Field Control Unit

Database

ESB Bus Node Units (ANB10 ) Connected per FCU

ER Bus Node Units (ANR10 )Connected per FCU

Total Number of ESB Bus Node Units ( ANB10 ) and ER Bus Node Units (ANR10 ) Connected per FCU

AFF50

Control Function for Compact Field Control Station (LFS1350)

Max. 3

Max. 3

Max. 3

AFG30

AFG40

Control Function for Enhance Field Control Station (LFS1330) with Node expanded databases

Max. 10

Max. 14

Max. 15

Others

Max. 10 (*1)

Max. 9 (*1)

Max. 10 (*1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1: In Case of AFG81 and AFG82 ,there are total number with SIO Nest (for CENTUM V or CENTUM-XL).

Total number of SIO: Max 5/FCU

 

Remote Node Connection

Yokogawa ER Bus Node Unit ANR10D-423

ER Bus: Max.4/FCU

When connecting a ER Bus Node Unit to a ESB Bus Node Unit or Field Control Unit, install ER Bus Interface Master Module (EB401) to the ESB Bus Node Unit or Field Control Unit.

To make single configuration, EB401 must be installed in an odd-number slot, and make a space on the right side of the installed EB401.

See “ER Bus Interface Master Module (for FIO)” (GS 33K50F40-50E) for further information.

 

Power Supply

Specify with Suffix Codes

Voltage: 100-120 V AC, Frequency: 50/60 Hz

Voltage: 220-240 V AC, Frequency: 50/60 Hz

Voltage: 24 V DC

 

Electric Power Consumption

100-120 V AC: 200 VA, 120 W

220-240 V AC: 230 VA, 120 W

24 V DC: 5.5 A

 

Weight

10 kg (including 8 I/O Modules)

 

Mounting

19-inch Rack Mounting

             Rack mount (M5 x 4 screws)

             Insulation bash (accessory)

 

Regulatory Compliance

For the detailed information of following standards, see System Overview (GS 33K01A10-50E).

Safety Standards

     [CSA]                    (for 100-120 V AC and 24 V DC power supply)

     [CE Marking]        (for 100-120 V AC, 220-240 V AC and 24 V DC power supply)

EMC Conformity Standards

    [CE Marking]          (for 100-120 V AC, 220-240 V AC and 24 V DC power supply)

    [C-Tick Marking]    (for 220-240 V AC and 24 V DC power supply)

    [KC Marking]         (for 100-120 V AC, 220-240 V AC and 24 V DC power supply)

Standards for Hazardous Location Equipment

     [CSA Non-Incendive]    (for 100-120 V AC and 24 V DC power supply)

     [FM Non-Incendive]      (for 100-120 V AC, 220-240 V AC and 24 V DC power supply)

     [Type n]                        (for 24 V DC power supply)

 

External Dimensions:  

Yokogawa ER Bus Node Unit ANR10D-423

 

 ANB10D, ANB10S external dimension.jpg

 

 

Models and Suffix Codes:   

Yokogawa ER Bus Node Unit ANR10D-423

anr10d suffix.jpg

 

Note: T-type Connector of ER Bus (YCB146) is supplied with ANR10 .

*1: Select the option code “/ATDOC” to follow the ATEX Directive for use in potentially explosive atmospheres.

*2: It must be sure to specify the Option Code “/NDEL” to connect with ANR10 with AFF50 or AFV10 .