Yokogawa Node Unit SNS10D for Dual Redunant ESB has an interface function to transmit analog input signals and contact signals from the field to the safety control unit via an ESB bus. Yokogawa Node Unit SNS10D for Dual Redunant ESB


 Detailed description

Yokogawa Node Unit SNS10D for Dual Redunant ESB


STANDARD SPECIFICATIONS

Number of Connectable Safety Node Units

Up to 13 safety node units can be connected to

SSC60S/SSC60D safety control unit using SEC402

ESB bus coupler module.

Up to 9 safety node units can be connected to SSC50S/SSC50D/SSC10S/SSC10D safety control unit using SEC401 ESB bus coupler module.

 

Power Supply Voltage

Yokogawa Node Unit SNS10D for Dual Redunant ESB

The power supply voltage is specified in the suffix codes.

Voltage: 100 to 120 V AC and 50/60 Hz frequency Voltage: 220 to 240 V AC and 50/60 Hz frequency Voltage: 24 V DC

 

Power Consumption

Yokogawa Node Unit SNS10D for Dual Redunant ESB

100 to 120 V AC specification: 200 VA

220 to 240 V AC specification: 230 VA

24 V DC specification: 5.5 A

 

Weight

Approximately 5.9 kg

 

Mounting Method

Yokogawa Node Unit SNS10D for Dual Redunant ESB

Rack mounting: Rack mount with four M5 screws

Insulation bushes (accessories) are used.

 

CONFIGURATION

Module Configuration

Yokogawa Node Unit SNS10D for Dual Redunant ESB

Power supply module: Supplies power to I/O module and transmitter (two modules)

The power supply terminal uses M4 screws.

ESB bus interface module (SSB401): two modules


RESTRICTIONS AND CAUTIONS FOR MOUNTING

Regarding the mounting of I/O modules on the safety node unit, there are restrictions in terms of quantity and slot position.