Brief

Yokogawa Node Unit ANR11D-415/NDEL for Dual Redunant ER BUS Yokogawa Node Unit ANR11D-415/NDEL for Dual Redunant ER BUS


 Detailed description

Yokogawa Node Unit ANR11D-415/NDEL for Dual Redunant ER BUS

 

The ESB Bus Node Unit has an interface function that communicates the analog I/O signals and contact I/O signals of a field with a Field Control Unit (FCU) via an ESB bus, as well as a function that supplies power to the I/O Modules.

This node units are connected to FCU via ESB bus.

 

 

Yokogawa Node Unit ANR11D-415/NDEL for Dual Redunant ER BUS

 

Hardware specifications

Yokogawa Node Unit ANR11D-415/NDEL for Dual Redunant ER BUS


No. of Node Units Connectable

Vnet/IP

 

Field Control Unit

Database

Total Number of ESB Bus Units (ANB10 ) and Optical ESB Bus Node Units (ANB11 ) Connectd per FCU

AFV30

AFV40

(*1)

Control Function for Field Control Station (LFS1700)

Max. 3

Control Function for Field Control Station (LFS1700) plus Node Expansion Package (LFS1750-V1)

Max. 9

Control Function for Field Control Station (LFS1700) plus Node Expansion Package (LFS1750-V2)

Max. 13

 

 

 

 

 

 

 

 

 

 

 

 



*1: Up to 11 node units per 1 cabinet can be installed in AFV40 .

 

 

Field Control Unit

Database

ESB Bus Node Units (ANB10 ) Connected per FCU

ER Bus Node Units (ANR10 )Connected per FCU

Total Number of ESB Bus Node Units ( ANB10 ) and ER Bus Node Units (ANR10 )Connected per FCU

AFV10

Control Function for Field Control Station (LFS1500)

Max. 3

Max. 3

Max. 3

Control Function for Field Control Station (LFS1500) plus Application Capacity Expansion Package (LFS1550)

Max. 9

Max. 14

Max. 14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vnet

Field Control Unit

Database

ESB Bus Node Units (ANB10 ) Connected per FCU

ER Bus Node Units (ANR10 )Connected per FCU

Total Number of ESB Bus Node Units ( ANB10 ) and ER Bus Node Units (ANR10 ) Connected per FCU

AFF50

Control Function for Compact Field Control Station (LFS1350)

Max. 3

Max. 3

Max. 3

AFG30

AFG40

Control Function for Enhance Field Control Station (LFS1330) with Node expanded databases

Max. 10

Max. 14

Max. 15

Others

Max. 10 (*1)

Max. 9 (*1)

Max. 10 (*1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*1: In Case of AFG81 and AFG82 ,there are total number with SIO Nest (for CENTUM V or CENTUM-XL).

Total number of SIO: Max 5/FCU

 


ESB Bus Node Connection


When connecting an ESB Bus Node Unit to FCU, install ESB Bus Couple Module (EC401 or EC402) to FCU (*1).

EC401 or EC402 must be installed in slot 7 and slot 8. To make single configuration, EC401 or EC402 must be installed in slot 7, and slot 8 must be empty.

   *1: AFV30 , AFV40 , AFV10 , or AFF55 .

 

Power Supply

Yokogawa Node Unit ANR11D-415/NDEL for Dual Redunant ER BUS

Specify with Suffix Codes

Voltage: 100-120 V AC, Frequency: 50/60 Hz

Voltage: 220-240 V AC, Frequency: 50/60 Hz

Voltage: 24 V DC

 

Electric Power Consumption

100-120 V AC: 200 VA, 120 W

220-240 V AC: 230 VA, 120 W

24 V DC: 5.5 A

 

Weight

10 kg (including 8 I/O Modules)

 

Mounting

19-inch Rack Mounting

             Rack mount (M5 x 4 screws)

             Insulation bash (accessory)

 

Regulatory Compliance

Yokogawa Node Unit ANR11D-415/NDEL for Dual Redunant ER BUS


Safety Standards

     [CSA]                    (for 100-120 V AC and 24 V DC power supply)

     [CE Marking]        (for 100-120 V AC, 220-240 V AC and 24 V DC power supply)

EMC Conformity Standards

    [CE Marking]          (for 100-120 V AC, 220-240 V AC and 24 V DC power supply)

    [C-Tick Marking]    (for 220-240 V AC and 24 V DC power supply)

    [KC Marking]         (for 100-120 V AC, 220-240 V AC and 24 V DC power supply)

Standards for Hazardous Location Equipment

     [CSA Non-Incendive]    (for 100-120 V AC and 24 V DC power supply)

     [FM Non-Incendive]      (for 100-120 V AC, 220-240 V AC and 24 V DC power supply)

     [Type n]                        (for 24 V DC power supply)