Product Information

Pepperl+Fuchs Switch Amplifier KCD2-SR-Ex1.LB[Product print page]

Product Name: Pepperl+Fuchs Switch Amplifier KCD2-SR-Ex1.LB
Product Type: KCD2-SR-Ex1.LB
Exhibitors: Pepperl+Fuchs
Product Documentation: No Related Documents

Brief

Pepperl+Fuchs Switch Amplifier KCD2-SR-Ex1.LB Pepperl+Fuchs Switch Amplifier KCD2-SR-Ex1.LB 1-channel isolated barrier


 Detailed description

  • Home
  • Explosion Protection
  • Products
  • Isolated Barriers
  • K-System
  • Switch Amplifier


Pepperl+Fuchs Switch Amplifier KCD2-SR-Ex1.LB

P+F Switch Amplifier KCD2-SR-Ex1.LB

Pepperl+Fuchs Isolated Barrier Switch Amplifier KCD2-SR-Ex1.LB


Features

Pepperl+Fuchs Switch Amplifier KCD2-SR-Ex1.LB


  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Dry contact or NAMUR inputs
  • Usable as signal splitter (1 input and 2 outputs)
  • Relay contact output
  • Fault relay contact output
  • Line fault detection (LFD)
  • Housing width 12.5 mm
  • Up to SIL2 acc. to IEC 61508
Function 


This isolated barrier is used for intrinsic safety applications. It transfers digital signals (NAMUR sensors/mechanical contacts) from a hazardous area to a safe area. 

The proximity sensor or switch controls a form A normally open relay contact for the safe area load. The normal output state can be reversed using switch S1. Switch S2 allows output II to be switched between a signal output and an error message output. Switch S3 enables or disables line fault detection of the field circuit. Pepperl+Fuchs Switch Amplifier KCD2-SR-Ex1.LB

During an error condition, relays revert to their de-energized state and LEDs indicate the fault according to NAMUR NE44. A unique collective error messaging feature is available when used with the Power Rail system. Pepperl+Fuchs Switch Amplifier KCD2-SR-Ex1.LB

Due to its compact housing design and low heat dissipation, this device is useful for detecting positions, end stops, and switching states in space-critical applications. Pepperl+Fuchs Switch Amplifier KCD2-SR-Ex1.LB