Product Information

Yokogawa ProSafe-RS Analog Input Module SAI143-H63/PRP[Product print page]

Product Name: Yokogawa ProSafe-RS Analog Input Module SAI143-H63/PRP
Product Type: SAI143-H63/PRP
Exhibitors: Yokogawa
Product Documentation: No Related Documents

Brief

Yokogawa ProSafe-RS Analog Input Module SAI143-H63/PRP Yokogawa Safety Instrumented Systems (SIS) Yokogawa ProSafe-RS Analog Input Module SAI143-H63/PRP


 Detailed description

Yokogawa Safety Instrumented Systems (SIS)

Yokogawa ProSafe-RS

 

Yokogawa ProSafe-RS Analog Input Module SAI143-H63/PRP          

 

STANDARD SPECIFICATIONS

Current Input Module

This module inputs 4 to 20 mA signals from the field.

The SAI143 can be made dual redundant.

 

Yokogawa ProSafe-RS Analog Input Module SAI143-H63/PRP

Item

Specfications

Model

SAI143 (*1)

Number of input channels

16-channel, module isolation (*5)

Rated input range

4 to 20 mA

Permissible input range

0 to 25 mA

Input impedance during P-ON

272.5  (20 mA) to 362.5  (4 mA)

Input impedance during P-OFF

500 k minimum

 

Rated accuracy

SAI143-S : ±16 µA (Input range 1 to 23 mA)

SAI143-H : ±16 µA (Input range 0.05 to 23 mA) (*3) (*4)

Data update frequency

40 ms

Temperature drift

±16 µA/10 °C

 

Transmitter power supply

16.15 V minimum (at 20 mA)

26.4 V maximum (at 0 mA) (Output current limit: 25 mA)

 

2/4-wire setting

Individual channel setting

Changed by setting pins

Withstand voltage

1.5 kV AC between input signal and system (*2)

 

Maximum current consumption

5 V system: 320 mA,

24 V system: 550 mA

 

Weight

0.34 kg (For pressure clamp terminal block or MIL cable)

0.39 kg (With signal cable interface adapter)

 

External connection

Pressure clamp terminal

MIL cable

Dedicated signal cable

Support PRM

Available (SAI143-H)

 

*1:      No Zener barriers can be connected to this module. An isolation barrier should be used when an intrinsic safety instrumented system is used.

*2:      500 V AC when dedicated signal cable is used. Yokogawa ProSafe-RS Analog Input Module SAI143-H63/PRP

*3:      ±32 µA (input range under 0.05 mA) (Style code S3 or later)

*4:      Rated accuracyof style code S3 or later is ±16 µA (Input range 0.05 to 23 mA).

Rated accuracy of style code S2 or earlieris ±16 µA (Input range 1 to 23 mA). Yokogawa ProSafe-RS Analog Input Module SAI143-H63/PRP

*5:      When SAI143-S£3 or SAI143-H£C is used in the ambienttemperature more than 60°C, number of input channels which a user can use is restricted. Refer to “ProSafe-RS Outline of I/O Modules (GS 32Q06K20-31E)”.

 

 

MODEL AND SUFFIX CODES

Yokogawa ProSafe-RS Analog Input Module SAI143-H63/PRP

 

 

Description

Model

SAI143

Analog Input Module (4 to 20 mA, 16-channel, module isolation)

 

 

 

 

 

Suffix Codes

-S

Standard type

-H

With HART communication [Release: R1.02.00] (*1)

     5

For pressure clamp terminal block or MIL cable with no explosion protection

     6

With signal cable interface adapter and no explosion protection (*2)

     E

For pressure clamp terminal block or MIL cable with explosion protection

     F

With signal cable interface adapter and explosion protection (*2)

          3

With ISA Standard G3 and temperature (-20 to 70 ºC)

          C

With ISA Standard G3 and high-density installation (-20 to 70 ºC) (*5)

 

 

 

 

 

 

Option Codes

 

/A4S00

With pressure clamp terminal block for analog

[Model: STA4S-00]

 

/A4S10

With pressure clamp terminal block for analog (with surge absorber) [Model: STA4S-10]

 

/A4D00

With dual-redundant pressure clamp terminal block for analog (*3) [Model: STA4D-00]

 

/A4D10

With dual-redundant pressure clamp terminal block for analog (with surge absorber) (*3) [Part name: STA4D-10]

/PRP

With prevention pin of false insertion (*4)

 

/CCC01

With connector cover for MIL cable (for flat ribbon cable) [Model: SCCC01]

 

*1:      For dual-redundant pressure clamp terminal block, please do not use STA4D-£0 S1.

*2:      When selecting SAI143-£6£or -£F£, you can not choose the option code of pressure clamp terminal block and MIL cable connector.

*3:      When using this module in a dual-redundant configuration, order an additional module with the same specifications but without option codes.

*4:      When SAI143-£6£or -£F£is selected, you can choose the option code for prevention pin of false insertion.

A mechanismto prevent wrong type I/O module insertion is supported with signal cable. The signal cable used with this I/O module must have option code /SAI143.

*5:     Suffix code for “With ISA StandardG3 and high-density installation” is available in case of SAI143-H£C. This is not available in case of SAI143-S.