Yokogawa Analog Output Module AAI543-H00/K4A00
Current Output Module (Isolated)
Yokogawa Analog Output Module AAI543-H00/K4A00 provides 16 outputs of 4 – 20 mA signal. Yokogawa Analog Output Module AAI543-H00/K4A00 can be used in dual-redundant configuration. (*1)
Items
Specifications
Model
AAI543-£5£/-£E£
AAI543-£6£/-£F£ (*2)
Number of output channels
16, isolated, standard switch-over
response in redundant configuration (*3)
16, isolated, fast switch-over response in
redundant configuration (*3)
Output signal
4 to 20 mA
Withstanding voltage
Between output and system: 1500 V AC, for 1 minute (*4)
Allowable load resistance
0 to 750 Ω
Circuit-open detection
Less than 0.65 mA
Accuracy
±48 µA
Data update period
10 ms
Drift due to ambient temperature change
±16 µA/10 ˚C
Maximum current consumption
230 mA (5 V DC), 540 mA (24 V DC)
Weight
Approx. 0.40 kg
External communication
Pressure clamp terminal, MIL connector cable, dedicated cable (KS1)
HART communication
Available
*1: A dual-redundant configuration is enabled by using two identical modules with the same suffix codes.
*2: When Yokogawa Analog Output Module AAI543-H00/K4A00 is installed in a node unit that conforms to the temperature environment, use it in the ambient temperature within 0 to 60 ºC range.
*3: When a switch over from control to stand-by module takes place in the dual-redundant configuration, the maximum period of time when the field output falls below 4 mA is 100 ms for Yokogawa Analog Output Module AAI543-H00/K4A00 (standard switch-over response) and 2 ms for AAI543-£6£/-£F£ (fast switch-over response). In case of connecting fast response type field devices, use AAI543-
£6£/-£F£ (fast switch-over response) in the dual-redundant configuration.
*4: When the dedicated cable is used, the withstanding voltage is 500 V AC (between the input signal and the system). When
the ML connector cable is used, the withstanding voltage depends on the electrical specifications of the cable.
MODEL AND SUFFIX CODES
Description Model AAI543 Analog Output Module (4 to 20 mA, 16-channel, Isolated) Suffix Codes -S Standard type -H With digital communication (HART protocol) 5 Standard switch-over response in redundant configuration with no explosion protection(*1) 6 Fast switch-over response in redundant configuration with no explosion protection(*2) E Standard switch-over response in redundant configuration with explosion protection(*1) F Fast switch-over response in redundant configuration with explosion protection(*2) 0 Basic type 1 With ISA Standard G3 option 3 With ISA Standard G3 option and temperature (-20 to 70 °C) option Option Codes /K4A00 With KS Cable Interface Adapter (For connecting AEA4D Terminal Board) [Model: ATK4A-00] /A4S00 With Pressure Clamp Terminal Block [Model: ATA4S-00] /A4S10 With Pressure Clamp Terminal Block (surge absorber) [Model: ATA4S-10] /A4D00 With Dual Pressure Clamp Terminal Block [Model: ATA4D-00] /A4D10 With Dual Pressure Clamp Terminal Block (surge absorber) [Model: ATA4D-10] /CCC01 With Connector Cover for MIL Cable [Model: ACCC01]
Description
AAI543
Analog Output Module (4 to 20 mA, 16-channel, Isolated)
Suffix
Codes
-S
Standard type
-H
With digital communication (HART protocol)
5
Standard switch-over response in redundant configuration with no explosion protection(*1)
6
Fast switch-over response in redundant configuration with no explosion protection(*2)
E
Standard switch-over response in redundant configuration with explosion protection(*1)
F
Fast switch-over response in redundant configuration with explosion protection(*2)
0
Basic type
1
With ISA Standard G3 option
3
With ISA Standard G3 option and temperature (-20 to 70 °C) option
Option
/K4A00
With KS Cable Interface Adapter (For connecting AEA4D Terminal Board) [Model: ATK4A-00]
/A4S00
With Pressure Clamp Terminal Block [Model: ATA4S-00]
/A4S10
With Pressure Clamp Terminal Block (surge absorber) [Model: ATA4S-10]
/A4D00
With Dual Pressure Clamp Terminal Block [Model: ATA4D-00]
/A4D10
With Dual Pressure Clamp Terminal Block (surge absorber) [Model: ATA4D-10]
/CCC01
With Connector Cover for MIL Cable [Model: ACCC01]
*1: If “standard switch-over response in redundant configuration” is selected, “basic type” or “with ISA Standard G3 option and temperature (-20 to 70 °C) option” may be specified.
*2: If “fast switch-over response in redundant configuration” is selected, “basic type” or “with ISA Standard G3 option” may be specified.
Contact Number: +86 13724889019 Email: tekrachel2024@163.com Web: www.tek-international.com WeChat: tekrachel tekrachel@163.com
Add.: Room 2401 Building D Greenland Central Plaza, Science City, Huangpu District, Guangzhou 510663, Guangdong Province, China.