Yokogawa Duplexed Field Control Unit AFS20D-H4123 Yokogawa Duplexed Field Control Unit AFS20D-H4123 the intelligence part in the Field Control Station (FCS)


 Detailed description

Yokogawa Duplexed Field Control Unit AFS20D-H4123

 

Hardware Specifications

Yokogawa Duplexed Field Control Unit AFS20D-H4123

For the installation specifications and the environmental conditions common to the systems, refer to “System Overview (GS 33K01A20-50E).”

 

Processor

VR5432 (133 MHz)

 

Main Memory Capacity

AFS20S, AFS20D: 16 Mbyte

AFG20S, AFG20D: 32 Mbyte

 

Memory Protection During Power Failure

Battery

Battery Back-up for Main Memory: Max. 72 hours

Battery Recharge Time: Min. 48 hours

 

FCU Status Contact Output

Yokogawa Duplexed Field Control Unit AFS20D-H4123

Three terminals (NC, NO, C)

Contact Points open or closed during FCU failure

Contact Rating:

Rated voltage: 250 V AC, max. 30 V DC

Rated current: Max. 2 A

Rated power supply: Max. 125 VA

 

Communication Interface

V net interface: Dual-redundant

RIO bus interface: Dual-redundant or single

 

No. of Nodes Connectable

Max. 8 Nodes

 

Power Supply

(specify with Suffix Codes)

Voltage: 100-120 V AC, Frequency: 50/60 Hz

Voltage: 220-240 V AC, Frequency: 50/60 Hz

Voltage: 24 V DC

 

Electric Power Consumption

100-120 V AC: 1700 VA (at max. node installation)

220-240 V AC: 2000 VA (at max. node installation)

24 V DC: 50 A (at max. node installation)

 

Weight

Approx. 250 kg (excluding nodes)

Approx. 400 kg (at maximum node installation)

 

Connection

Power Supply: M6 screw terminal connection (dual power system possible)

Grounding: M8 bolt terminal connection

Contact Output: M4 screw terminal connection

 

Paint Color

Main body: Frosty white (Munsell No. 2.5 Y 8.4/1.2)

Channel base: Spring black (Munsell No.3.3PB2.5/0.5)

 

Channel Base Option Specification

Channel base with hole for cable: (Option Code:/CH)

A hole for cables, 300 (length) by 40 mm (width) is opened at the rear of the channel base (with filler plate at time of delivery).

 

IP Protection Rating

IP20

 

Regulatory Compliance

Yokogawa Duplexed Field Control Unit AFS20D-H4123

For the detailed information of following standards, see Integrated Production Control System CENTUM VP System Overview (GS 33K01A20-50E)

Safety Standards

[CSA]          (for 100-120 V AC power supply)

[CE Marking]    (for 220-240 V AC power supply)

EMC Conformity Standards

[CE Marking]   (for 220-240 V AC and 24 V DC power supply)

[C-Tick Marking] (for 220-240 V AC and 24 V DC power supply)

 

External Dimensions

Yokogawa Duplexed Field Control Unit AFS20D-H4123

AFS20S AFS20D AFG20S AFG20D external dimension.jpg

 

Model and Suffix Codes

Yokogawa Duplexed Field Control Unit AFS20D-H4123

 

 

Description

Model

AFS20D

Duplexed Field Control Unit (for Vnet and RIO, with Cabinet)

Suffix Codes

-H

Standard Type (Main Memory 16 Mbyte )

    4

Dual-Redundant V net, Dual-Redundant RIO bus

       1

Single AC Power System

       2

Dual AC Power System

           1

100-120 V AC Power Supply

           2

220-240 V AC Power Supply

           4

24 V DC Power Supply

                3

LFS1100 Basic software license for Control Function for Standard Field Control Station (for V net and RIO, for CP345)

Option Codes

-NDF4

Node Interface Unit for Dual-Redundant RIO bus, Dual Power Supply Attached to Front Side of FCU(*2)

-NDR4

Node Interface Unit for Dual-Redundant RIO bus, Dual Power Supply Attached to Rear Side of FCU(*2)

/CH

Channel Base with cable hole (*1)

/CE

With CE Marking and C-Tick Marking and KC Marking (*3)

 

*1: AFS20D with this option code (/CH) does not have CE Marking, C-Tick Marking or KC Marking.

*2: Fill the installation quantity in the . Total no. installable is 6.

-NDF4 (Attached to front side of FCU). Total no. installable is 3.

-NDR4 (Attached to rear side of FCU). Total no. installable is 3.

*3: Change to conductive gasket.