Product Information

Yokogawa Field Control Unit AFF50S-H31401[Product print page]

Product Name: Yokogawa Field Control Unit AFF50S-H31401
Product Type: AFF50S-H314011
Exhibitors: Yokogawa
Product Documentation: No Related Documents

Brief

Yokogawa Field Control Unit AFF50S-H31401 covers the hardware specifications of the Field Control Unit. Yokogawa Field Control Unit AFF50S-H31401


 Detailed description

Yokogawa Field Control Unit AFF50S-H31401


GENERAL

Yokogawa Field Control Unit AFF50S-H31401
This GS covers the hardware specifications of the Field Control Unit which is the processor of the Field Control Station (FCS).

HARDWARE SPECIFICATIONS

Yokogawa Field Control Unit AFF50S-H31401
For the installation specifications and the environmental conditions common to the systems, refer to “System Overview (GS 33K01A20-50E).”
Power Supply
(specify with Suffix Codes)
Voltage:  100-120 V AC, Frequency: 50/60 Hz Voltage:  220-240 V AC, Frequency: 50/60 Hz Voltage:  24 V DC
Power Consumption
100-120 V AC:  200 VA (AFF50S-H314011/D)
220-240 V AC:  230 VA (AFF50S-H314011/D)
24 V DC:  5.5 A (AFF50S-H314011/D)
Weight
Approx. 7 kg (AFF50S-H314011) Approx. 8 kg (AFF50D)
Mounting
19-inch Rack Mounting:
Rack mount (M5x8 screws) Insulation bush (accessory)
Connection
Power Supply:  M4 screw terminal connection Grounding:  M4 screw terminal connection Contact Output: M4 screw terminal connection


MODELS AND SUFFIX CODES
Field Control Unit (19-inch Rack Mountable Type)

Yokogawa Field Control Unit AFF50S-H31401

 

 

Description                                          

Model

AFF50S

Field Control Unit (for V net and FIO, for 19-inch Rack Mountable)

 

 

 

 

 

 

Suffix Codes

-H

Compact type

3

Dual-Redundant V net (10BASE-2), Single power supply

4

Dual-Redundant V net (10BASE-2), Dual-Redundant power supply

1

Always 1

1

100–120 V AC power supply

2

220–240 V AC power supply

4

24 V DC

0

Basic type

1

With ISA Standard G3 option

 

1

LFS1350 Basic software license for Control Function for Compact Field Control Unit

(for V net and FIO)

Option Code

/ATDOC

Explosion Protection Manual (*1)

 *1: Select the option code "/ATDOC" to follow the ATEX Directive for use in potentially explosive atmospheres.


Yokogawa Field Control Unit AFF50S-H31401