Product Information

Yokogawa I/O Expansion Cabinet ACB41-S1120[Product print page]

Product Name: Yokogawa I/O Expansion Cabinet ACB41-S1120
Product Type: ACB41-S1120
Exhibitors: Yokogawa
Product Documentation: No Related Documents

Brief

Yokogawa I/O Expansion Cabinet ACB41-S1120 can be mounted beside a field control unit(FCU) or separately. Yokogawa I/O Expansion Cabinet ACB41-S1120


 Detailed description

Yokogawa I/O Expansion Cabinet ACB41-S1120


GENERAL

Yokogawa I/O Expansion Cabinet ACB41-S1120
The I/O Expansion Cabinet is used to install a Node Unit (NU) and Compact Field Control Unit (for FIO).  It can be mounted beside a field control unit (FCU) or separately. A Node Unit and Compact Field Control Unit (for FIO) can be installed at the front and rear of the cabinet.


HARDWARE SPECIFICATIONS

Yokogawa I/O Expansion Cabinet ACB41-S1120
For the installation specifications and environmental conditions that are common to the systems, refer to “System Overview (GS 33K01A20-50E).”
Installable NU Type
Node Unit: Rack mountable type
Duplexed Node Unit: Rack mountable type Compact Field Control Unit (for FIO): AFF50S Compact Duplexed Field Control Unit (for FIO):
AFF50D
Max. No. of Installable NU
The installation patterns shown below are selectable.
Max. 4 AFF50 (Front side: 2, Rear end: 2)
1 AFF50 + Max.3 Node Unit (Front side) Max. 8 Node Unit (Front side: 4, Rear end: 4)
Fan Alarm Contact Output Three terminals (NC, NO, C) Contact Rating:
Rated voltage: 30 V DC Rated current: Max. 0.3 A
Power Supply
(specify with Suffix Codes)
Voltage: 100-120 V AC, Frequency: 50/60 Hz Voltage: 220-240 V AC, Frequency: 50/60 Hz Voltage: 24 V DC
Power Consumption
100-120 V AC:  1700 VA (at max. node installation)
220-240 V AC:  1900 VA (at max. node installation)
24 V DC:  46 A (at max. node installation)
Connection
Power Supply:  M6 screw terminal connection
(Dual power supply is also possible) Grounding:  M8 bolt terminal connection
Weight
Approx. 400 kg (at max. installation)


MODELS AND SUFFIX CODES
I/O Expansion Cabinet

Yokogawa I/O Expansion Cabinet ACB41-S1120

 

 

Description

Model

ACB41

I/O Expansion Cabinet (for FIO)

 

Suffix

Codes

-S

Standard Type

1

Front/Rear: For Node Unit Mounting

 

2

Front: For Node Unit Mounting

Rear: For 19-inch Rack Equipment Mounting

 

3

Front: For 19-inch Rack Equipment Mounting (*3) Rear: For 19-inch Rack Equipment Mounting

0

No Power Supply (Applies only to -S3) (*3)

1

Single Power System

2

Dual Power System

0

No Power Supply (Applies only to -S3) (*3)

1

100-120 V AC Power Supply

2

220-240 V AC Power Supply

4

24 V DC Power Supply

0

Always 0

 

Option

Codes

 

/£-5S3

Field Control Unit [Model/Suffix Code : AFF50S-H3££01] Single Power System and Dual-Redundant V net

 

/£-5S4

Field Control Unit [Model/Suffix Code : AFF50S-H4££01] Dual-Redundant Power System and Dual-Redundant V net

 

/£-5D4

Duplexed Field Control Unit [Model/Suffix Code : AFF50D-H4££01] Dual-Redundant Power System and Dual-Redundant V net

/£-S1L

Node Unit for Single ESB Bus and Single Power Supply [Model/Suffix Code: ANB10S-3£5/NDEL] (*4)

 

/£-S2L

Node Unit for Single ESB Bus and Dual-Redundant Power Supply

[Model/Suffix Code: ANB10S-4£5/NDEL] (*4)

 

/£-D2L

Node Unit for Dual-Redundant ESB Bus and Dual-Redundant Power Supply

[Model/Suffix Code: ANB10D-4£5/NDEL] (*4)

/££-S81

Node Unit for Single ESB Bus and Single Power System (*2)

/££-S82

Node Unit for Single ESB Bus and Dual-Redundant Power System (*2)

/££-D82

Node Unit for Dual-Redundant ESB Bus and Dual-Redundant power supply (*2)

/££-R81

Node Unit for Single ER Bus and Single power supply (*2)

/££-R82

Node Unit for Single ER Bus and Dual-Redundant power supply (*2)

/££-B82

Node Unit for Dual-Redundant ER Bus and Dual-Redundant power supply (*2)

/CH

Channel Base with cable hole (*1)

/CE

With CE Marking, C-Tick Marking and KC Marking

/ATDOC

Explosion Protection Manual (*5)


Note: When mounting an AFF50 and ANB10 in one cabinet, only the following combinations are available: “/1-5S3” and “/-S1L” “/1-5S4” and “/-S2L” “/1-5D4” and “/-D2L”
The combination with ER bus node unit ANR10 is not available.
*1:ACB41-S1120 with this option code (/CH) does not have CE Marking, C-Tick Marking or KC Marking.
*2:When installing the different type of Node in one cabinet, only the following combinations are available:
-S81 and -R81, -S82 and -R82, -D82 and -B82
Fill the installation quantity in the . Total no. installable is 08.
In case of standard order, the ESB bus node unit is installed first in the front and top of the cabinet, then ER bus node unit. ESB bus connector unit and ESB bus cable are installed inside the cabinet. For between cabinet and ER bus cable wiring, please order separately.
*3:If you specify this suffix code -S3000, a fan is not supplied with ACB41-S1120.
*4:Order an EC401 separately when ordering “/1-5S3” or “/1-5S4”, and 2 EC401 separately when ordering “/1-5D4”.
*5:Select the option code “/ATDOC” to follow the ATEX Directive for use in potentially explosive atmospheres.


Yokogawa I/O Expansion Cabinet ACB41-S1120