Yokogawa Relay Output Module ADR541
GENERAL
This GS covers the hardware specifications of Yokogawa Relay Output Module ADR541 that can be installed in the ESB Bus Node Unit (ANB10S, ANB10D), Optical ESB Bus Node Unit (ANB11S, ANB11D), and the Field Control Unit (AFV30S, AFV30D, AFV40S, AFV40D).
Relay Output Module
Yokogawa Relay Output Module ADR541 The Relay Output Module outputs the 16-channel relay contact signals. It can be used in dual redundant configuration.
Item
Specifications
Model
ADR541
Number of output channels
16
Rated applied voltage
24 to 110 V DC, 100 to 240 V AC, 50/60 Hz
Maximum load current (*1)
Resistive load:
24 V DC: 2.0 A/channel, 110 V DC: 0.4 A/channel
100 V AC: 2.0 A/channel, 220 V AC: 2.0 A/channel
Inductive load:
24 V DC: 0.6 A/channel, 110 V DC: 0.1 A/channel
100 V AC: 1.0 A/channel, 220 V AC: 1.0 A/channel
Withstanding voltage
Between output signal and system: 2 kV AC, For 1 minute
Between commons: 1.35 kV AC, For 1 minute, common minus (–) side every 8-channel
Functions Status output Pulse width output
Time-proportioning output
ON/OFF status output function
One-shot pulse width output function
Time-proportioning ON/OFF
Output response time
12 ms or less (for status output) 20 ms or less (for mixed status and pulse outputs)
Pulse width
40 ms to 7200 s
Pulse width resolution
8 ms, but ON/OFF delay added for maximum 10 ms
Maximum current consumption
780 mA (5 V DC)
Weight
Approx. 0.30 kg
External connection
Pressure clamp terminal, Dedicated cable (AKB334)
Relay switching life
100000 operations (*2)
Note: The signals connected the same common should be the same phase when applying AC voltage. *1: Maximum 8 A is allowed per common. Connect a spark killer diode when driving DC relay. *2: The relay cannot be replaced with new one. If it comes to the end of its life, the module should be replaced.
MODELS AND SUFFIX CODES
Description Model ADR541 Relay Output Module (16-channel, 24 to 110 V DC/100 to 240 V AC, Isolated) Suffix Codes -P With pulse width output function/time-proportional output function 5 Without status display; with no explosion protection E Without status display; with explosion protection 0 Basic type 3 With ISA Standard G3 option and temperature (-20 to 70 °C) option Option Code /C4S70 With Pressure Clamp Terminal Block for Digital Input [Model : ATC4S-70]
Description
Relay Output Module (16-channel, 24 to 110 V DC/100 to 240 V AC, Isolated)
Suffix
Codes
-P
With pulse width output function/time-proportional output function
5
Without status display; with no explosion protection
E
Without status display; with explosion protection
0
Basic type
3
With ISA Standard G3 option and temperature (-20 to 70 °C) option
Option
Code
/C4S70
With Pressure Clamp Terminal Block for Digital Input [Model : ATC4S-70]
Contact Number: +86 13724889019 Email: tekrachel2024@163.com Web: www.tek-international.com WeChat: tekrachel tekrachel@163.com
Add.: Room 2401 Building D Greenland Central Plaza, Science City, Huangpu District, Guangzhou 510663, Guangdong Province, China.