Product Information

Yokogawa Relay Output Module ADR541[Product print page]

Product Name: Yokogawa Relay Output Module ADR541
Product Type: ADR541
Exhibitors: Yokogawa
Product Documentation: No Related Documents

Brief

Yokogawa Relay Output Module ADR541 installed in the ESB Bus Node Unit (ANB10S, ANB10D), Optical ESB Bus Node Unit (ANB11S, ANB11D). Yokogawa Relay Output Module ADR541


 Detailed description

Yokogawa Relay Output Module ADR541


GENERAL

Yokogawa Relay Output Module ADR541

This GS covers the hardware specifications of Yokogawa Relay Output Module ADR541 that can be installed in the ESB
Bus Node Unit (ANB10S, ANB10D), Optical ESB Bus Node Unit (ANB11S, ANB11D), and the Field Control Unit
(AFV30S, AFV30D, AFV40S, AFV40D).


Relay Output Module

Yokogawa Relay Output Module ADR541
The Relay Output Module outputs the 16-channel relay contact signals.
It can be used in dual redundant configuration.

Item

Specifications

Model

ADR541

Number of output channels

16

Rated applied voltage

24 to 110 V DC, 100 to 240 V AC, 50/60 Hz

Maximum load current (*1)

Resistive load:

24 V DC: 2.0 A/channel, 110 V DC: 0.4 A/channel

100 V AC: 2.0 A/channel, 220 V AC: 2.0 A/channel

Inductive load:

24 V DC: 0.6 A/channel, 110 V DC: 0.1 A/channel

100 V AC: 1.0 A/channel, 220 V AC: 1.0 A/channel

 

Withstanding voltage

Between output signal and system: 2 kV AC, For 1 minute

Between commons: 1.35 kV AC, For 1 minute, common minus (–) side every 8-channel

Functions Status output Pulse width output

Time-proportioning output

 

ON/OFF status output function

One-shot pulse width output function

Time-proportioning ON/OFF

Output response time

12 ms or less (for status output) 20 ms or less (for mixed status and pulse outputs)

Pulse width

40 ms to 7200 s

Pulse width resolution

8 ms, but ON/OFF delay added for maximum 10 ms

Maximum current consumption

780 mA (5 V DC)

Weight

Approx. 0.30 kg

External connection

Pressure clamp terminal, Dedicated cable (AKB334)

Relay switching life

100000 operations (*2)

 Note: The signals connected the same common should be the same phase when applying AC voltage.

*1: Maximum 8 A is allowed per common. Connect a spark killer diode when driving DC relay.
*2: The relay cannot be replaced with new one. If it comes to the end of its life, the module should be replaced.


MODELS AND SUFFIX CODES

Yokogawa Relay Output Module ADR541


 

 

Description

Model

ADR541

Relay Output Module (16-channel, 24 to 110 V DC/100 to 240 V AC, Isolated)

 

 

Suffix

Codes

-P

With pulse width output function/time-proportional output function

5

Without status display; with no explosion protection

E

Without status display; with explosion protection

0

Basic type

3

With ISA Standard G3 option and temperature (-20 to 70 °C) option

Option

Code

 

/C4S70

 

With Pressure Clamp Terminal Block for Digital Input [Model : ATC4S-70]