Yokogawa Analog I/O Module AAP849-S01
GENERAL
Yokogawa Analog I/O Modules AAP849-S01 Installed in the ESB bus node units (ANB10S and ANB10D), Optical ESB bus node units (ANB11S and ANB11D), and field control units (for FIO) (AFV30S, AFV30D, AFV40S, AFV40D, AFV10S, AFV10D). The Yokogawa Analog I/O Module AAP849-S001 function as signal converters; by inputting field analog signals into these modules, it converts them to internal data for field control stations (FCS), or the FCS’s internal data to analog signals for outputs.
HART Communication Functional Specifications
The analog I/O modules (with HART communication function) are equipped with HART modems and eable HART communication (*1) by directly connecting the HART devices to he modules. No. of HART devices: Max. 16 devices/module HART variables: Max. 32 points/module HART variables can be treated as ordinary process input data via %Z terminal connection. It is just for input. HART multidrop connection (*2): Max. 5 devices/channel HART variables data refresh cycle time : 1 second/device (When maximum of 16 devices are connected, it is 17 seconds per ESB bus connection.)
Contact Number: +86 13724889019 Email: tekrachel2024@163.com Web: www.tek-international.com WeChat: tekrachel tekrachel@163.com
Add.: Room 2401 Building D Greenland Central Plaza, Science City, Huangpu District, Guangzhou 510663, Guangdong Province, China.