Product Information

Yokogawa Analog I/O Module AAP849-S01[Product print page]

Product Name: Yokogawa Analog I/O Module AAP849-S01
Product Type: AAP849-S01
Exhibitors: Yokogawa
Product Documentation: No Related Documents

Brief

Yokogawa Analog I/O Modules AAP849-S01


 Detailed description

Yokogawa Analog I/O Module AAP849-S01


GENERAL

Yokogawa Analog I/O Modules AAP849-S01
Installed in the ESB bus node units (ANB10S and ANB10D), Optical ESB bus node units (ANB11S and ANB11D), and field control units (for FIO) (AFV30S, AFV30D, AFV40S, AFV40D, AFV10S, AFV10D).
The Yokogawa Analog I/O Module AAP849-S001 function as signal converters; by inputting field analog signals into these modules, it converts them to internal data for field control stations (FCS), or the FCS’s internal data to analog signals for outputs.


HART Communication Functional Specifications

Yokogawa Analog I/O Module AAP849-S01

The analog I/O modules (with HART communication function) are equipped with HART modems and eable HART
communication (*1) by directly connecting the HART devices to he modules.
No. of HART devices: Max. 16 devices/module
HART variables:  Max. 32 points/module
HART variables can be treated as ordinary process input data via %Z terminal connection. It is just for input.
HART multidrop connection (*2):  Max. 5 devices/channel
HART variables data refresh cycle time :
1 second/device (When maximum of 16 devices are connected, it is 17 seconds per ESB bus connection.)