Yokogawa Analog I/O Modules AAR181-S53
GENERAL
Yokogawa Analog I/O Modules AAR181-S53 This document describes about hardware specifications of Yokogawa Analog I/O Modules AAR181-S53 to be installed in the ESB bus node units (ANB10S and ANB10D), Optical ESB bus node units (ANB11S and ANB11D), and field control units (for FIO) (AFV30S, AFV30D, AFV40S, AFV40D, AFV10S, AFV10D). TheseYokogawa Analog I/O Modules AAR181-S53 function as signal converters; by inputting field analog signals into these modules, it converts them to internal data for field control stations (FCS), or the FCS’s internal data to analog signals for outputs.
HART Communication Functional Specifications
The analog I/O modules (with HART communication function) are equipped with HART modems and eable HART communication (*1) by directly connecting the HART devices to he modules. No. of HART devices: Max. 16 devices/module HART variables: Max. 32 points/module HART variables can be treated as ordinary process input data via %Z terminal connection. It is just for input. HART multidrop connection (*2): Max. 5 devices/channel HART variables data refresh cycle time : 1 second/device (When maximum of 16 devices are connected, it is 17 seconds per ESB bus connection.) *1: HART communication refers to HART variable communicaiton, on-demand communication, and hand held terminal (HHT) communication. *2: It is possible to connect only input devices. This connection does not support analog data value nor burst function
Contact Number: +86 13724889019 Email: tekrachel2024@163.com Web: www.tek-international.com WeChat: tekrachel tekrachel@163.com
Add.: Room 2401 Building D Greenland Central Plaza, Science City, Huangpu District, Guangzhou 510663, Guangdong Province, China.